Product Manual

Configuring Basic Settings
975-0638-01-01 Rev E 4–7
Configuring Basic Settings
An overview of the Conext SW Basic Settings menu structure is shown below.
Figure 4-3 Menu Map of the Conext SW Basic Settings
[*Flooded] [Gel] [AGM]
[*250Ah] [50Ah] to [1000Ah]
[*80%] [10%] to [100%]
[*3Stage] or [2StgNoFloat]
[*25.0V] [22.0V]to [29.0V]
[*30.0A] [5.0A]to [30.0A]
[*21.0V] [20.0V]to [24.0V]
CSW4024 00: Basic
Batt Type
Batt Capacity
Max Chg Rate
Charge Cycle
ReCharge Volts
AC In Breaker
Low Batt Cut Out
[Flooded]
[220Ah]
[80%]
[3Stage]
[25.0V]
[30.0A]
[21.0V]
Follow procedures on β€œTo select and change a configurable setting:” on
page 4–4 to change the settings.
Tabl e 4-1 Setting Defaults and Ranges
Model 24-volt Models 48-volt Model
Item Default Min Max Default Min Max
Batt Type Flooded Flooded, Gel,
AGM, Custom
Flooded Flooded, Gel,
AGM, Custom
Batt Capacity 250Ah 50Ah 100Ah 250Ah 50Ah 1000Ah
Max Chg Rate 100% 10% 100% 100% 10% 100%
Charge Cycle 3Stage 3Stage,
2StgNoFloat
3Stage 3Stage,
2StgNoFloat
ReCharge Volts 25.0V 22.0V 29.0V 50.0V 44.0V 58.0V
AC In Breaker 30A 5A 30A 30A 5A 30A
Low Batt Cut
Out
21.0V 20.0V 24.0V 42.0V 40.0V 48.0V
Tabl e 4-2 Basic Settings
Item Description
Batt Type Sets the system battery chemistry and type: Flooded,
AGM, Gel, and Custom.
Batt Capacity Selects the system battery capacity in amp hours.
ConextSW-NA-OwnersGuide.book Page 7 Thursday, July 23, 2015 3:26 PM