Product Manual

Configuration via SCP
4–8 975-0638-01-01 Rev E
Max Chg Rate Sets the percentage of the maximum DC output current
that is available to the charger. The maximum DC output
current for different models is:
SW 2524 120/240 — 65 ADC
SW 4024 120/240 — 90 ADC
SW 4048 120/240 — 45 ADC
If multiple Conext SWs are charging the same battery
bank, set each inverter's Max Chg Rate to 1/n of the
desired charge rate (where n is the number of inverter/
chargers).
Charge Cycle Sets the charging method: 3-Stage (bulk, absorption,
float) or 2StgNoFloat (bulk, absorption, no float).
ReCharge Volts Sets the recharging volts to tell the charger to initiate
charging when the battery drains past the value setting.
AC In Breaker Sets the breaker limit of incoming AC (generator or grid).
Low Batt Cut Out Low Battery Cut Out (LBCO) controls when the inverter
stops producing AC output due to a low battery voltage
condition. The inverter will stop producing AC output only
after this level has been reached for the period of time set
by the LBCO Delay. This setting is not temperature
compensated.
Tabl e 4-2 Basic Settings