Configuring Advanced Settings
Inverter Settings Menu
The Inverter Settings menu contains settings that control when the Conext SW
starts and stops producing AC output.
NOTICE
RISK OF DAMAGE TO CONNECTED DEVICES
The advanced settings are intended for qualified installation/service personnel
only. Before changing advanced settings, you must be familiar with the
settings and the system-wide impact of changing those settings. Setting
parameters incorrectly could damage connected equipment (such as
batteries) or could severely affect the performance of your system. Incorrect
charging configuration can lead to battery damage.
Failure to follow these instructions can result in equipment damage.
Figure 4-4 Inverter Settings Menu Screen
CSW4024 00: Inv
Low Batt Cut Out
LBCO Hysteresis
LBCO Delay
Hi Batt Cut Out
Search Watts
Search Delay
Inv Block Start
Inv Block Stop
[21.0]
[2.0V]
[10sec]
[29.0V]
[50W]
[2sec]
[hh:mm AM]
[hh:mm AM]
CSW4024 00: Adv
Inverter Settings
Charger Settings
AC Settings
Gen Support
Multi Unit Config
Restore Defaults
Adv Features
[*21.0V] [20.0V] to [24.0V]
[*10sec] [0sec] to [600sec]
[*29.0V] [29.0V] to [34.0V]
[*50W] [5W] to [250W]
[*2sec] [1sec] to [25sec]
[*2.0V] [0.5V] to [5.0V]
Follow procedures on β€œTo select and change a configurable setting:” on page 4–6 to
change the settings.
Tabl e 4-3 Setting Defaults and Ranges
Model 24-volt Models 48-volt Model
Item Default Min Max Default Min Max
Low Batt Cut
Out
21.0V 20.0V 24.0V 42.0V 40.0V 48.0V
LBCO Hysteresis 2.0V 0.5V 5.0V 2.0V 0.5V 5.0V
LBCO Delay 10sec 0sec 600sec 10sec 0sec 600sec
Hi Batt Cut Out 29.0V 29.0V 34.0V 68.0V 58.0V 68.0V
Search Watts 50W 5W 250W 50W 5W 250W
Search Delay 2sec 1sec 25sec 2sec 1sec 25sec
Inv Block Start 12:00AM n/a 12:00AM n/a
Inv Block Stop 12:00AM n/a 12:00AM n/a