Product Manual

Configuration via SCP
4–14 975-0638-01-01 Rev E
ReCharge Volts 25.0V 22.0V 27.0 50.0V 44.0V 58.0V
Absorb Time 180min 1min 480min 180min 1min 480min
Auto Chg Enable
Disabled
Enabled,
Disabled
Disabled
Enabled,
Disabled
Chg Block Start 12:00AM n/a 12:00AM n/a
Chg Block Stop 12:00AM n/a 12:00AM n/a
Tabl e 4-6 Charger Settings Menu Description
Item Description
Batt Type Sets the system battery chemistry and type: Flooded, AGM, Gel,
and Custom.
Selecting Custom displays the Custom Settings item, which
allows you to adjust the settings for each charging stage.
Custom
Settings
See page 4–19.
LithiumIon
Settings
See page 4–21.
Batt
Capacity
See page 4–7.
Max Chg
Rate
Same description as “Basic Settings” on page 4–7.
Charge
Cycle
Sets the charging method: 3Stage (bulk, absorption, float) or
2StgNoFloat (bulk and absorption only, no float).
Default
Batt Temp
Selects the battery temperature charging compensation if a
battery temperature sensor is not installed. In the absence of a
battery temperature sensor, the charger uses one of three
settings:
Cold (50 °F/10 °C), Warm (77 °F/25 °C), or Hot (104 °F/40 °C).
ReCharge
Volts
Sets the recharging volts to tell the charger to initiate charging
when the battery drains past the value setting.
Absorb
Time
Sets the maximum time spent in the absorption stage, before
transitioning to float or no float.
NOTE: The Absorb Time setting resets to its default value of 180
minutes when the Battery Type is changed except when changing
to Custom Settings. In Custom Settings, the Absorb Time setting
will not reset to its default value.
Tabl e 4-5 Setting Defaults and Ranges
Model 24-Volt Models 48-Volt Model
Item Default Min Max Default Min Max
ConextSW-NA-OwnersGuide.book Page 14 Thursday, July 23, 2015 3:26 PM