Configuring Advanced Settings
975-0638-01-01 Rev E 4–23
Figure 4-8 AC Settings Menu Screen
Table 4-15 Setting Defaults and Ranges
Model All Models
Item Default Min Max
ACIn Breaker 30A 5A 30A
ACIn Lo Volt 95V 78V 115V
ACIn Hi Volt 135V 125V 140V
ACIn Lo Freq 55Hz 44Hz 59Hz
ACIn Hi Freq 65Hz 61Hz 70Hz
CSW4024 00: Adv
Inverter Settings
Charger Settings
AC Settings
AC Support
Multi Unit Config
Restore Defaults
Adv Features
CSW4024 00: AC
ACIn Breaker
ACIn Lo Volt
ACIn Hi Volt
ACIn Lo Freq
ACIn Hi Freq
[30.0A]
[190.0V]
[270.0V]
[55Hz]
[65Hz]
[*190.0V] [156.0V] to [230.0V]
[*30A] [5A] to [30A]
[*270.0V] [250.0V] to [280.0V]
[*55Hz] [44Hz] to [59Hz]
[*55Hz] [61Hz] to [70Hz]
Follow procedures on “To select and change a configurable setting:” on page 4–6 to
change the settings.
Table 4-16 AC Settings menu
Item Description
ACIn Breaker Sets the AC Input breaker size, based on the size of the
installed AC breaker at the source. The Breaker size setting
must not exceed the capacity of the AC source such as the
grid or a generator. The Conext SW limits the maximum input
current to this setting by derating its charging current. If the
connected loads exceed the breaker setting, the AC breaker
trips. The breaker may not trip if Load Shave is enabled and
Load Shave Amps is configured not to exceed the AC source’s
rated output current.
ACIn Lo Volt Sets the minimum acceptable AC input voltage level from the
AC source (generator or grid).
NOTE: It is recommended to leave this setting to its default
value and not to set it to the maximum allowed. Doing so might
inadvertently derate charging power in jurisdictions where the
nominal AC mains voltage or generator output is at 110 volts.