Configuring Advanced Settings
975-0638-01-01 Rev E 4–27
an
4. Set the battery SOC thresholds for when AC support mode is engaged.
Load Shaving Setting
For Load shaving to be effective, all loads must be connected to the inverter. For
large loads, stacked Conext SW inverters may be required. To help the batteries
supplement the power requirements of the connected load, an additional source
of power (like solar, wind, or hydroelectric) is recommended but not required.
To demonstrate a scenario where load shaving takes effect on the Conext SW,
the following settings are programmed into the SCP.
Scenario Settings: Load Shave=Enabled
LoadShaveAmps=10A
LoadShaveStart=6:00AM
LoadShaveStop=9:00PM
PLSDelay=Enabled
To use the Load Shaving feature:
1. Enable load shaving.
CSW4024 00: AC Support
LoadShaveStart
LoadShaveStop
AC Supp on Soc
AC Supp Start Soc
[12:00 AM]
[12:00 AM]
[Enabled]
[80%]
From AC Support -> AC Support on SOC
Press Enter, then select Enabled using the
up and down arrow buttons. Press Enter.
CSW4024 00: AC Support
LoadShaveStop
AC Supp on Soc
AC Supp Start Soc
AC Supp Stop Soc
[12:00 AM]
[Enabled]
[80%]
[20%]
From AC Support -> AC Supp Start Soc
Press Enter, then select a value using the up
and down arrow buttons. Press Enter.
Press Enter, then select a value using the up
and down arrow buttons. Press Enter.
From AC Support -> AC Supp Stop Soc
CSW4024 00: AC Support
AC Supp Mode
AC Supp Volts
Load Shave
Load Shave Amps
[Disabled]
[26.0V]
[Enabled]
[24A]
CSW4024 00: Adv
Inverter Settings
Charger Settings
AC Settings
AC Support
Multi Unit Config
Restore Defaults
Adv Features
Go to Advanced Settings -> AC Support -> Load Shave
Press Enter, then select Enabled using the up and down arrow
buttons. Press Enter.