Product Manual

Configuration via SCP
4–30 975-0638-01-01 Rev E
Figure 4-10 Multi Unit Config Menu Screen
CSW4024 00: Adv
Inverter Settings
Charger Settings
AC Settings
AC Support
Multi Unit Config
Restore Defaults
Adv Features
CSW4024 00: Multi
Dev Name
Dev Number
Invtr Mode
AC In
Battery
[CSW4024]
[00]
[Master]
[Gen1]
[HouseBatt1]
[*Master] [Slave]
[*Gen1] [Grid1]
[*HouseBatt1]...[HouseBatt5]
Follow procedures on “To select and change a configurable setting:” on page 4–6 to
change the settings.
IMPORTANT: Accessing this menu automatically places the Conext SW in
standby mode. When entering the Multi Unit Config menu, the unit identifies
itself by flashing all front panel LEDs. After exiting the Multi Unit Config menu,
the Conext SW returns to operating mode and the front panel LEDs stop flashing.
Table 4-18 Multi Unit Menu Description and Values
a
a.Applies to all Conext SW models.
Item Description Default Range
Dev Name Allows the customizing
of the default name for
the inverter/charger.
This setting is optional
and does not affect
operation. See “Setting
the Device Name” on
page 4–31.
CSW4024
will vary from model
to model.
Can be
changed by
the user.
Dev Number Allows setting of a
unique unit number in a
multiple-unit system.
See “Setting the Device
Number” on page 4–32.
00 usually for a
single unit or for two
units, this will
designate the
master.
00
31
Invtr Mode For this to operate, one
Conext SW must be
configured to Master
and the other as Slave,
otherwise a system-wide
fault is asserted.
Master Master,
Slave
AC In For identifying the type
of AC source when two
power sources are
available and an AGS is
also present.
Gen1 Gen1, Grid1
Battery For identifying batteries
only.
HouseBatt1 HouseBatt1..
HouseBatt5
ConextSW-NA-OwnersGuide.book Page 30 Thursday, July 23, 2015 3:26 PM