Product Manual

Configuration via SCP
4–34 975-0638-01-01 Rev E
EuroFreq Feature
The default inverter AC output frequency is 60 Hz.
To change the inverter AC output frequency to 50 Hz:
1. Put the system in Standby mode. See “To change an operational setting” on
page 3–18.
2. Change the EuroFreq to Enabled. See “To select and change a configurable
setting:” on page 4–6.
3. Restore the system to Operating mode. See “To change an operational
setting” on page 3–18.
StoreInv
State
See “Storing the State of the
Inverter Mode” on page 1–13.
Enabled Enabled,
Disabled
AcCouple
For information on this feature
refer to the AC Coupling
Solutions Guide.
Disabled Enabled,
Disabled
Enhanced
ACSup
See “Enhanced AC Support”
on page 1–8.
Disabled Disabled,
Enabled
PLSDelay
Delays load shaving and AC
support features until the
MPPT has charged the battery
in float mode for 2 hours. See
“Grid-Interactive Delay
Feature” on page 1–11.
Disabled Disabled,
Enabled
NoLoadVD
See “NoLoadVD” on page 1–
13.
Disabled Enabled,
Disabled
a.Applies to all Conext SW models.
Table 4-19 Adv Features Description and Values
a
Item Description Default Range
NOTICE
EQUIPMENT DAMAGE
Do not change the frequency to 50 Hz unless the equipment and appliances
connected to the inverter’s output can operate in this frequency setting.
Failure to follow these instructions can result in equipment damage.
IMPORTANT: Restoring to default (see “Restoring Factory Default Settings” on
page 4–33) means that the AC output frequency will change back to 60 Hz.
ConextSW-NA-OwnersGuide.book Page 34 Thursday, July 23, 2015 3:26 PM