Product Manual

Configuration via SCP
4–36 975-0638-01-01 Rev E
Multi
Unit
Config
Dev Name
Select unique device Name for each unit
CSW4024
CSW2524
CSW4048
Dev Number
Select unique device number for each unit
00 00
Invtr Mode
Select Master or Slave designation for each unit
Master Master
AC In
Select AC source type
Gen1 Gen1
Battery
Identify batteries
HouseBatt1 HouseBatt1
Restore
Defaults
Restore Defaults
Restores all system default settings
-- --
Advanced
Features
EuroFreq
Sets AC output frequency to 50 Hertz
Disabled Disabled
StoreInv
State
Sets inverter mode state feature.
Enabled Enabled
AcCouple
Sets AC Coupling feature. See “AC Coupling” on page 1–12.
Disabled Disabled
Enhanced ACSup
Sets enhanced AC Support feature. See “Enhanced AC
Support” on page 1–8.
Disabled Disabled
PLSDelay
Sets load shaving delay for 2 hours. See “Grid-Interactive
Delay Feature” on page 1–11.
Disabled Disabled
NoLoadVD
Sets no load voltage derating feature. See “NoLoadVD” on
page 1–13.
Disabled Disabled
SETTING DESCRIPTION
DEFAULT
24-volt
DEFAULT
48-volt
YOUR
SETTING
ConextSW-NA-OwnersGuide.book Page 36 Thursday, July 23, 2015 3:26 PM