Installation Guide
© 2020 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. January, 2021 tc
Document Number: F-27393-16
www.schneider-electric.com
schneider-electric.com | 1Installation Instruction
SpaceLogic VBB/VBS
Ball Valves with Floating Actuators
Inspection
Inspect the package for damage. If package is damaged,
notify the appropriate carrier immediately. If undamaged, open
the package and inspect the device for obvious damage.
Return damaged products.
Requirements
RISK OF EQUIPMENT DAMAGE
• Read and understand these instructions before installing or
servicing this product.
• Do not install this product in hazardous or classified
locations unless expressly permitted.
• Turn off all power supplying equipment before working on
the product.
• Make all connections in accordance with the electrical wiring
diagram.
• Do not exceed the product’s technical ratings.
• Use copper conductors only. Make all connections in
accordance with the appropriate electrical wiring diagram.
• Avoid installation locations exposed to vibration, excessive
moisture, and/or corrosive or explosive vapours.
• Avoid electrical noise interference. Do not install near large
conductors, electrical machinery, or welding equipment.
• When making wiring connections within the actuator, do not
put leads or connectors below the motor.
• This product is a class 2 (Limited Voltage Limited Energy)
device.
• The installer is responsible for conformance to all applicable
codes.
• Check the Electrical terminals and any configuration switch
settings before powering up the actuator.
Failure to follow these instructions may cause equipment
damage.
If this product is used in a manner not specified by the manufacturer,
the protection provided by the product may be impaired.
No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this product.
NOTICE
Tools (not provided)
• Wrench/adjustable spanners 1”…1-5/8”
• Pipe wrench according to pipe size
• Volt-ohm multimeter
• Phillips Head screwdriver
Training and Other Accessories
• Installer must be a qualified, experienced technician
• Other accessories as appropriate.
A
B
AB
Two-Way Valve: Flow A to AB Three-Way Valve: Mixing Only A
and/or B to AB.
M332A0x
M312A0x or M322A0x
Mounting
The valves can be mounted in horizontal or vertical piping.
When installed in horizontal piping, the actuator must be
above the valve body. When installed in horizontal piping the
actuator can be tilted left or right but it must not be tilted below
45° from vertical.
Vertical Pipe
90
Horizontal Pipe
Horizontal Plane