Product Specifications

MASKED PRODUCT IMAGE
Conext SW Inverter/charger
Technical Specications - North America
MASKED PRODUCT IMAGE
© 2016 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
Device short name SW 2524 120/240 SW 4024 120/240 SW 4048 120/240
Electrical specifications - inverter
Output power (continuous) at 25°C 3000 W 3400 W 3800 W
Output power (30 min) at 25°C 3300 W 4000 W 4400 W
Output power (5 sec) at 25°C 5000 W 7000 W 7000 W
Peak current 24.3 A 41 A 41 A
Output frequency 50 / 60 Hz selectable 50 / 60 Hz selectable 50 / 60 Hz selectable
Output voltage 120 / 240 Vac 120 / 240 Vac 120 / 240 Vac
Output wave form True sine wave True sine wave True sine wave
Optimal efficiency 91.5% 92% 94%
Idle consumption search mode <11 W <11 W <11 W
Input DC voltage range 20 - 34 Vdc 20 - 34 Vdc 40 - 68 Vdc
AC connections Single / Split phase Single / Split phase Single / Split phase
Electrical specifications - charger
Output current 65 A 90 A 45 A
Nominal output voltage 24 Vdc 24 Vdc 48 Vdc
Output voltage range 12 - 32 Vdc 12 - 32 Vdc 24 - 64 Vdc
Charge control 2 or 3 stage 2 or 3 stage 2 or 3 stage
Charge temperature compensation Yes - BTS included Yes - BTS included Yes - BTS included
Optimal efficiency 90% 90% 92%
AC input power factor > 0.98 > 0.98 > 0.98
Input current 9 A 13 A 12 A
Input AC voltage 120 / 240 Vac split phase 120 / 240 Vac split phase 120 / 240 Vac split phase
Input AC voltage range line to neutral 95 - 135 Vac single phase 95 - 135 Vac single phase 95 - 135 Vac single phase
170 - 270 Vac 170 - 270 Vac 170 - 270 Vac
Dead battery charge Yes Yes Yes
General specifications
Tare loss 24 W 29 W 27 W
Compatible battery types FLA, Gel, AGM, Custom FLA, Gel, AGM, Custom FLA, Gel, AGM, Custom
Transfer relay rating 30 A 30 A 30 A
Transfer time (AC to inverter and inverter to AC) <1 cycle (16.7 ms) <1 cycle (16.7ms) <1 cycle (16.7 ms)
Optimal operating temperature range -20°C to 60°C (-4°F to 140°F) -20°C to 60°C (-4°F to 140°F) -20°C to 60°C (-4°F to 140°F)
Storage ambient temperature range -40°C to 85°C (-40°F to 185°F) -40°C to 85°C (-40°F to 185°F) -40°C to 85°C (-40°F to 185°F)
Humidity Operation / storage < 95% RH, non condensing < 95% RH, non condensing < 95% RH, non condensing
Ingress protection rating Indoor only, IP20 Indoor only, IP20 Indoor only, IP20
Altitute (operating) 2000 m (6562 ft) 2000 m (6562 ft) 2000 m (6562 ft)
Product weight 22.3 kg (49.0 lb) 28.1 kg (62.0 lb) 28.1 kg (62.0 lb)
Shipping weight 27.2 kg (60.0 lb) 35.0 kg (77.1 lb) 35.0 kg (77.1 lb)
Product dimensions (H x W x D) 41.8 x 34.1 x 19.7 cm 41.8 x 34.1 x 19.7 cm 41.8 x 34.1 x 19.7 cm
(16.5 x 13.4 x 7.6 in) (16.5 x 13.4 x 7.6 in) (16.5 x 13.4 x 7.6 in)
Shipping dimensions (H x W x D) 56.0 x 44.0 x 32.0 cm 56.0 x 44.0 x 32.0 cm 56.0 x 44.0 x 32.0 cm
(22.0 x 17.3 x 12.6 in) (22.0 x 17.3 x 12.6 in) (22.0 x 17.3 x 12.6 in)
System network and remote monitoring Available Available Available
Warranty (Depending on the country of installation) 2 or 5 years 2 or 5 years 2 or 5 years
Part number 865-2524 865-4024 865-4048
Regulatory approvals
Safety c(CSA) us mark CSA C22.2, No. 107.1-01 UL1741 Ed.2
EMC FCC Part 15 Class B
Compatible products
Universal DC distribution panel 865-1016
AC distribution panel (120/240 V) 865-1017
Conext System Control Panel 865-1050-01
Conext Automatic Generator Start 865-1060-01
Conext ComBox 865-1058
Conext MPPT 80 600 or 60 150 solar charge controller 865-1032 or 865-1030-1
Conext SW On/Off Remote Switch 865-1052
Conext Battery Monitor 865-1080-01
Conext SW Stacking Kit 865-1019 for 120 / 240 Vac
Conext Configuration Tool 865-1155-01
Specifications are subject to change without notice.
DS20160624_ConextSW