Product Manual

Configuring Advanced Settings
975-0636-01-01 Rev E 4–13
Setting the Inv Block Start and Inv Block Stop to the same time disables
Inverter Block. Disabling Inverter Block means that inverting is allowed to occur
at any time when the right conditions for inverting exist.
NOTE: In a multiple unit configuration, set the same Inverter Block settings to
both the master and slave units.
Charger Settings Menu
The Charger Settings menu provides options for configuring the Conext SW to
operate from your battery bank.
Figure 4-5 Charger Settings Menu Screen
Tabl e 4-5 Setting Defaults and Ranges
Model 24-volt Models 48-volt Model
Item Default Min Max Default Min Max
Batt Type Flooded Flooded, Gel,
AGM, Custom,
LithiumIon
Flooded Flooded, Gel,
AGM, Custom,
LithiumIon
Custom Settings See page 4–19. See page 4–19.
LithiumIon
Settings
See page 4–19. See page 4–19.
Batt Capacity See page 4–7. See page 4–7.
Max Chg Rate 100% 10% 100% 100% 10% 100%
Charge Cycle 3Stage 3Stage,
2StgNoFloat
3Stage 3Stage,
2StgNoFloat
Default Batt
Temp
Warm Hot, Warm, Cold Warm Hot, Warm, Cold
CSW4024E 00: Chg
Batt Type
Custom Settings
LithiumIon Settings
Batt Capacity
Max Chg Rate
Charge Cycle
Default Batt Temp
ReCharge Volts
Absorb Time
Auto Chg Enable
Chg Block Start
Chg Block Stop
[Flooded]
[250Ah]
[100%]
[3-Stage]
[Warm]
[25.0V]
[180min]
[Enabled]
[hh:mm AM]
[hh:mm AM]
CSW4024E 00: Adv
Inverter Settings
Charger Settings
AC Settings
AC Support
Multi Unit Config
Restore Defaults
Adv Features
[*80%] [10%] to [100%]
[*250Ah] [50Ah] to [1000Ah]
[*3-Stage] or [2StgNoFloat]
[*Warm] [Hot] [Cold]
[*25.0V] [22.0V] to [29.0V]
[*180min] [1min] to [480min]
[*Enabled] or [Disabled]
[*Flooded] [Gel] [AGM] [Custom] [LithiumIon]
Follow procedures on “To select and change a configurable setting:” on page 4–6 to
change the settings.
ConextSWEUROwnersGuide.book Page 13 Thursday, July 23, 2015 3:32 PM