Setting the Chg Block Start and Chg Block Stop to the same time disables
Charger Block. Disabling Charger Block means that charging is allowed to occur
at any time when the right conditions for charging exist.
Custom Battery Settings Menu
The Custom Battery Settings menu can be viewed if Custom is selected as the
Batt Type. This menu allows you to adjust charging and equalization voltage for
batteries with specifications that fall outside the default settings for the battery
types the Conext SW offers. You can also adjust the temperature compensation
constant for the battery temperature sensor on this menu.
NOTICE
EQUIPMENT DAMAGE
Consult your battery manufacturer and associated documentation before
setting a custom battery type and before battery charging or equalization.
Failure to follow this instruction may cause damage to the battery.
Figure 4-6 Custom Settings Menu Screen
Table 4-11 Setting Defaults and Ranges
Model 24-volt Models 48-volt Model
Item Default Min Max Default Min Max
Eqlz Support Enabled Enabled,
Disabled
Enabled Enabled,
Disabled
Eqlz Voltage 32.0V 27.0V 32.0V 62.0V 54.0V 64.0V
Bulk Voltage 28.8V 27.2V 32.0V 57.6V 54.2V 64.0V
Absorb Voltage 28.8V 24.0V 32.0V 57.6V 40.0V 64.0V
Float Voltage 27.0V 22.0V 32.0V 54.0V 50.0V 64.0V
Batt Temp Comp -54mV/C -0mV/C -90mV/C
-108mV/C
-0mV/C
-108mV/C
CSW4024E 00: Cust
Eqlz Support
Eqlz Voltage
Bulk Voltage
Absorb Voltage
Float Voltage
BattTempComp
[Enabled]
[32.0V]
[28.8V]
[28.8V]
[27.0V]
[-54mV/C]
CSW4024E 00: Chg
Batt Type
Custom Settings
Batt Capacity
Max Chg Rate
Charge Cycle
[Custom]
[220Ah]
[100%]
[3-Stage]
Follow procedures on β€œTo select and change a configurable setting:” on page 4–6 to
change the settings.
Eqlz Voltage appears only
when Eqlz Support is
Enabled.
Custom Settings appears only when
Batt Type is set to Custom.