Product Manual
Configuring Advanced Settings
975-0636-01-01 Rev E 4β21
The LithiumIon Settings menu can be viewed if LithiumIon is selected as the
Batt Type. This menu allows you to adjust charging and equalization voltage for
batteries with specifications that fall outside the default settings for the battery
types the Conext SW offers.
Figure 4-7 LithiumIon Settings Menu Screen
Table 4-13 Setting Defaults and Ranges
Model 24-Volt Models 48-Volt Model
Item Default Min Max Default Min Max
Control 3-Stage Ext BMS,
2-Stage,
3-Stage
3-Stage Ext BMS,
2-Stage,
3-Stage
Bulk Voltage 29.0V 28.2V 32.5V 58.0V 56.2V 65.0V
Max Bulk
Current
90A 15A 90A 45A 10A 45A
Absorb Voltage 29.0V 20.0V 32.5V 58.0V 40.0V 65.0V
Max Absorb
Current
90A 15A 90A 45A 10A 45A
Float Voltage 26.8V 23.6V 32.0V 53.6V 47.2V 64.0V
Max Float
Current
90A 1A 90A 45A 1A 45A
DisChgImax 150% 20% 500% 150% 20% 500%
DisChgImax
Timer
10s 1S 300s 10s 1s 300s
Table 4-14 Custom Battery Settings Menu Description
Item Description
Control Identifies the kind of battery management system.
CSW4024E 00: Chg
Batt Type
LithiumIon Settings
Batt Capacity
Max Chg Rate
Charge Cycle
[LithiumIon]
[250Ah]
[100%]
[3Stage]
CSW4024E 00: LithiumIon
Control
Bulk Voltage
Max Bulk Current
Absorb Voltage
Max Absorb Current
Float Voltage
Max Float Current
DisChgImax
DisChgImax Timer
[3-Stage]
[29.0V]
[90A]
[29.0V]
[90A]
[26.8V]
[90A]
[150%]
[10s]
Follow procedures on βTo select and change a configurable setting:β on page 4β6 to
change the settings.
LithiumIon Settings appears only
when Batt Type is set to Custom.
ConextSWEUROwnersGuide.book Page 21 Thursday, July 23, 2015 3:32 PM