Product Manual

Configuring Advanced Settings
975-0636-01-01 Rev E 4–29
Multi Unit Config Menu
The Multi Unit Config menu configures the Conext SW to operate as a part of
a multiple unit installation
1
.
Figure 4-10 Multi Unit Config Menu Screen
1.In Conext SW Inverter/Chargers, multiple unit configuration (installation) is limited to two units -
one master unit and one slave unit.
IMPORTANT: Accessing this menu automatically places the Conext SW in
standby mode. When entering the Multi Unit Config menu, the unit identifies
itself by flashing all front panel LEDs. After exiting the Multi Unit Config menu,
the Conext SW returns to operating mode and the front panel LEDs stop flashing.
Table 4-18 Multi Unit Menu Description and Values
a
Item Description Default Range
Dev Name Allows the customizing
of the default name for
the inverter/charger.
This setting is optional
and does not affect
operation. See “Setting
the Device Name” on
page 4–30.
CSW4024E
will vary from
model to model.
Can be changed
by the user.
Dev Number Allows setting of a
unique unit number in a
multiple-unit system.
See “Setting the Device
Number” on page 4–31.
00 usually for a
single unit or for
two units, this will
designate the
master.
00
31
Invtr Mode For this to operate, one
Conext SW must be
configured to Master
and the other as Slave,
otherwise a system-wide
fault is asserted.
Master Master, Slave
CSW4024E 00: Adv
Inverter Settings
Charger Settings
AC Settings
Gen Support
Multi Unit Config
Restore Defaults
Adv Features
CSW4024E 00: Multi
Dev Name
Dev Number
Invtr Mode
AC In
Battery
[CSW4024E]
[00]
[Master]
[Gen1]
[HouseBatt1]
[*Master] [Slave]
[*Gen1] [Grid1]
[*HouseBatt1]...[HouseBatt5]
Follow procedures on “To select and change a configurable setting:” on page 4–6 to
change the settings.
ConextSWEUROwnersGuide.book Page 29 Thursday, July 23, 2015 3:32 PM