Default Settings and Ranges
975-0240-01-01 B–5
Grid Support Menu
Gen Support Menu
Aux Menu
Item
Default Range Step Size
Grid Supp Volts
53.0 V
a
a.The setting for Grid Supp Volts must be greater or equal to LBCO+2 V. For example, if
LBCO is 44 V then the minimum Grid Supp Volts is 46 V.
42.0–70.0 V
0.1
Sell Disabled Disabled, Enabled n/a
Max Sell Amps
b
b.This setting is restricted to the selected external AC1 breaker size.
27 A (XW+ 6848),
20 A (XW+ 5548)
0–27 A (XW+ 6848),
0–20 A (XW+ 5548)
1
Load Shave Disabled Disabled, Enabled n/a
Load Shave Amps 48 A 0–48 A 1
Load Shave Start
c
c.When Load Shaving is enabled, if Load Shave Start and Load Shave Stop are set to the
same time, the Conext load shaves continuously.
12:00 AM 12:00 AM–11:59 PM,
00:00–23:59
1
Load Shave Stop 12:00 AM 12:00 AM–11:59 PM,
00:00–23:59
1
Sell Block Start 12:00 AM 12:00 AM–11:59 PM,
00:00–23:59
1
Sell Block Stop 12:00 AM 12:00 AM–11:59 PM,
00:00–23:59
1
Setting Default Range Step Size
GenSupp Mode Disabled Enabled, Disabled n/a
GenSupp Amps 48 A 0–48 A 1
Item
Default Range
Step Size
Manual Aux ManualOff ManualOn, ManualOff,
Automatic
n/a
Active Lvl ActiveHigh ActiveHigh, ActiveLow n/a
Trig Src
a
LowBattV LowBattV, HighBattV,
LowBattTemp,
HighBattTemp, Fault
n/a
Trigger Level—
LowBattV
b
46.0 VDC 20.0–58.0 VDC
0.1
Clear Level—LowBattV
48.0 VDC 20.0–58.0 VDC
0.1
Trigger Level—HighBattV
56.0 VDC 48.0–64.0 VDC
0.1
Clear Level—HighBattV
52.0 VDC 48.0–64.0 VDC
0.1