Reading the Meters Screen
The Meters screen displays total system power production, grid voltage and
current status, and load voltage and current status.
To view the Meters screen:
On the Conext XW+ setup menu, highlight Meters and press Enter.
Search Search mode is enabled and the Conext XW+ is standing by, waiting to begin
inverting. See “Using Search Mode” on page 3–9.
SellToGrid The Conext XW+ is grid-tied and is exporting energy to the utility grid on AC1. Both
Grid Support and Sell must be enabled in order to sell power back to the utility. See
Table 3-1, “Conext XW+ Setup Menu” on page 3–2 and “Grid Support Settings” on
page 3–25. All configurations must comply with local and national electrical codes.
Standby The unit has been placed in standby mode using the Mode setting on the Conext SCP
Setup menu, the Standby button on the Conext SCP, or the Standby key press
(
STARTUP/SHUTDOWN and Equalization) on the inverter information panel.
Passthru The AC connected to the AC1 or AC2 input is passing directly through the Conext
XW+ to the loads attached to AC Out. The batteries are not being charged in this state.
Equalize Equalization has been turned on and the Conext XW+ is equalizing the batteries after
completing a full charge cycle.
Table 2-1 Conext XW+ Home Screen States
Conext XW+
Status
Displayed When...
Figure 2-8 Viewing the Meters Screen
XW+ 6848 00: Meters
4500VA 3200W
21.1A 120V
21.1A 120V
60Hz
0VA 0W
0.0 A0V
0.0 A0V
0Hz
4500VA 3200W
21.1A 120V
21.1A 120V
60Hz
Float
3.7A 57.4V
20 ° C
XW+ 6848 00: Setup
Meters
[Enabled]
[Disabled]
[Disabled]
[Enabled]
[Bulk]
[Disabled]
[Operating]