Product Manual
Monitoring Operation
2–18 975-0240-01-01
Table 2-2 Meters Screen
Screen Item Description
AC1 AC input power connected to the Conext XW+ AC1 terminals, in volt-amps and watts.
AC1 is assumed to be connected to the utility grid, but can be connected to any other
AC source.
AC1 in L1 AC input voltage and current connected to the Conext XW+ AC1 L1 terminals. This input
voltage display may drift slightly before the Conext XW+ has synchronized to the grid.
AC1 in L2 AC input voltage and current connected to the Conext XW+ AC1 L2 terminals. This input
voltage display may drift slightly before the Conext XW+ has synchronized to the grid.
AC1 Freq AC frequency connected to the Conext XW+ AC1 terminals.
AC2 AC input power connected to the Conext XW+ AC2 terminals, in volt-amps and watts.
AC2 is assumed to be connected to a generator, but can be connected to any other AC
source.
AC2 in L1 AC input voltage and current supplied to the Conext XW+ from the AC2 L1 input. This
meter indicates the Conext XW+ is drawing power from the generator to charge the
battery or power the AC loads.
AC2 in L2 AC input voltage and current supplied to the Conext XW+ from the AC2 L2 input. This
meter indicates the Conext XW+ is drawing power from the generator to charge the
battery or power the AC loads.
AC2 Freq AC frequency connected to the Conext XW+ AC2 terminals.
Load Power Power consumed by the AC loads attached to AC OUT, in volt-amps and watts.
Load L1 AC voltage and current supplied from L1 to the AC loads on AC OUT.
Load L2 AC voltage and current supplied from L2 to the AC loads on AC OUT.
Load Freq AC frequency supplied to the AC loads on AC OUT.
State Operating state of the Conext XW+. For more information, see Table 2-1 on page 2–15.
DC Charging current and battery voltage.
Batt Temp Battery temperature as read by the BTS, connected to the Conext XW+. If the BTS is
connected to a different device on the Xanbus network, please see the Meters screen for
that device for temperature data. All Xanbus devices on the Xanbus network will share
temperature data for temperature compensated charging. However, the temperature is
only displayed on the meters screen for the device with the BTS installed. The BTS which
is monitoring the device displaying the highest temperature will take priority. If the BTS is
not installed, it shows NotAvailable.
XW_Operation.book Page 18 Wednesday, August 12, 2015 2:39 PM