Inverter Settings Menu
The Inverter Settings menu contains settings that control when the Conext
XW+ starts and stops producing AC output.
For default settings, see “Inverter Settings Menu” on page B–3.
Table 3-2 Inverter Settings Menu
Item Description
Low Batt
Cut Out
Low Batt Cut Out controls when the inverter stops producing AC output due to a low battery
voltage condition. The inverter will stop producing AC output only after this level has been
reached for the period of time set by the LBCO Delay. This setting is not temperature
compensated.
LBCO
Delay
LBCO Delay controls how long the inverter is allowed to operate at or below the
Low Batt Cut Out level before turning off due to a low battery voltage condition. The
inverter will stop producing AC output only after the Low Batt Cut Out level has been
reached for this uninterrupted period of time.
Once the inverter has shut off, the battery voltage must rise 4 volts above the
Low Batt Cut Out setting for inverter operation to resume.
High Batt
Cut Out
High Batt Cut Out sets the maximum battery voltage at which the inverter will operate. If
the battery voltage exceeds this limit for more than 1 minute, the Conext XW+ displays a
fault message (F49) and shuts down. The inverter will not support AC loads when in this
condition. If a qualified AC source is present, the unit passes AC through to the loads. The
inverter automatically restarts when the voltage drops to 6 volts below the High Batt Cut
Out setting. If battery voltage continues to rise after shutdown, an external charger may still
be charging the batteries. The Conext XW+ cannot control how external chargers operate.
Search
Watts
Search Watts sets search sensitivity for the Conext XW+ when search mode is enabled.
When a load larger than this setting is present on AC OUT, the inverter starts producing AC
output from battery power. Enabling search mode from the Setup menu (see page 3–2) can
minimize power draw from the battery during periods of low demand from loads. Also see
“Using Search Mode” on page 3–9.
Search
Delay
Search Delay sets the time between search pulses. When searching for loads, the Conext
XW+ sends out search pulses on AC OUT to determine the presence of a load above
Search Watts. Conext XW+ power draw while in search mode decreases when Search
Delay is increased, but the Conext XW+ response time to active loads is slower.