Charger Settings Menu
975-0240-01-01 3–13
Figure 3-4 Three-Stage Battery Charging Cycle
Time
Time
Absorption Voltage
Float Voltage
Max Absorb Time - Default
3
hrs
(adjustable 1 min - 8 hrs)
Boost
Timer
1hr fixed
Absorption Exit Current
Threshold = 2% of
programmed AH capacity
3-Stage Charge
Custom Charge
Float StageAbsorption Stage
Bulk Stage
(Boost Stage)
Battery
Current
Max Charge
Rate
Battery
Voltage