Generator Support Settings
975-0240-01-01 3–35
For default settings, see “Gen Support Menu” on page B–5.
Gen support
mode
Battery
Voltage
[A]
AC In Current >
GenSupportA
AC In Current <
GenSupportA
V[LBCO]
V[DC max]
[LBCO]+2V
[exit]
[entry]
Gen Support Mode
Figure 3-9 Gen Support Mode Graph
Note: Ensure that the battery bank has sufficient energy to support your loads for
the anticipated time period, otherwise draining the battery to LBCO may put the
system in Fault mode.
Table 3-7 Gen Support Menu Values
Setting Description
GenSupp
Mode
Turns the generator support feature on and off.
GenSupp
Amps
Sets the generator load level at which the Conext XW+ begins
to convert external DC energy and supply additional AC
power in parallel to loads on AC Out.