Product Manual
Configuration
3–40 975-0240-01-01
Inverter
Mode
For a split-phase system: For a multi-unit system to
operate, one Conext XW+ must be configured to
SplitPhMaster and the rest as SplitPhSlave, otherwise
a system-wide fault is asserted.
SplitPhMaster
For single-
phase, three-
wire models:
SplitPhMaster,
SplitPhSlave
For a single-phase system:
For a multi-unit system to
operate, one Conext XW+ must be configured to
1PhMaster
and the rest as
1PhSlave
, otherwise a system-
wide fault is asserted.
Before setting up a single-phase system, perform the steps
in “Converting 120 V/240 V Split-Phase to 120 V Single-
Phase” in the
Conext XW+ Inverter/Charger Installation
Guide.
1PhMaster
SplitPhMaster,
SplitPhSlave
For a three-phase system: See “Three-Phase Configuration” on page 3–43.
Connections Select to display the Connections menu.
See “Connections Menu” on page 3–45.
n/a n/a
Table 3-9 Multi-Unit Config Menu
Item Description Default Range
XW_Operation.book Page 40 Wednesday, August 12, 2015 2:39 PM