Product Manual
Connections Menu
975-0240-01-01 3–45
Connections Menu
The Connections menu contains additional settings to allow the Conext XW+ to
function as part of a multi-unit networked system.
Setting the connections for a Xanbus-enabled device provides a way of
identifying non-network associations for Xanbus-enabled devices (see Figure 3-
11) and enhancing networked power system management. When connections
are set, devices of different types become associated and can share sources,
e.g. a common DC input source, or a common grid/generator source.
In multi-unit networked systems, multiple inverter/chargers can be stacked to
produce increased charge current. To achieve this functionality, the devices must
be configured to the same DC connection, such as House Battery Bank 1. The
units will collaborate on battery charging by communicating with other units on
this shared DC connection.
Table 3-10 Example Three-phase Inverter Assignments
Line or Phase Inverter Mode Role Assignment
a
a.Each phase can support one master unit and one slave unit.
Suggested
Device Number
Line-1 or Phase-A
3Ph L1 Master
b
b.The L1 Master is also the master Conext XW+ for the entire system. The system master
broadcasts phase synchronizing pulses through its sync port, and each phase master con-
trols the slave units on its respective phase.
Phase-A or Line-1 Master
10
3Ph L1 Slave
c
c.The slave unit in each phase is optional.
Phase-A or Line-1 Slave
11
Line-2 or Phase-B 3Ph L2 Master
Phase-B or Line-2 Master
20
3Ph L2 Slave
Phase-B or Line-2 Slave
21
Line-3 or Phase-C 3Ph L3 Master
Phase-C or Line-3 Master
30
3Ph L3 Slave
Phase-C or Line-3 Slave
31
WARNING
ADVANCED CONFIGURATION HAZARD
Advanced menu settings should be used by qualified personnel only.
Three phase operation should be configured by qualified personnel only.
Consult with the local utility before enabling Conext XW+ sell mode or grid
support functions.
Do not change these settings unless you are under the supervision and
direction of qualified personnel.
Failure to follow these instructions can result in death or serious injury.
XW_Operation.book Page 45 Wednesday, August 12, 2015 2:39 PM