Product Manual
Configuration
3–46 975-0240-01-01
For default settings, see “Connections Menu” on page B–6.
Note: When configuring clusters of three Conext XW+ units (or a grouping of up
to six in a grid-tie application), each cluster’s DC connections must be set to the
same battery bank. If one of the units is set with a different DC connection, a
system configuration fault (F66) occurs.
Table 3-11 Connections Menu
Item Description
DCConn DC input and output connection. This is the common DC connection
shared between the Conext XW+, charge controllers, and referenced
by the Conext Automatic Generator Start.
ACOut AC output connection. This connection specifies a common AC
output connection shared between Conext XW+ units. The AC output
connection has to be configured so that the units know if they are
connected to the same load or not. If connected to the same load,
select the same name on all units; for example, “ACLoad1.” If
connected to separate load banks, use different names for the AC
output connection on each unit; for example, “ACLoad1” on one unit
and “ACLoad2” on the other.
AC1 AC1 input connection. This connection specifies a common
AC port 1 input for multiple Conext XW+ units.
AC2 AC2 input connection. This connection specifies a common
AC port 2 input for multiple Conext XW+ units.
Figure 3-11 Conext XW+ Connections Representation
L1 N L2 L1 N L2 L1 N L2
AC
LOAD
GRID
(AC1)
GEN
(AC2)
AC OUT AC IN AC IN
DC Connection:
Select House Battery 1 to 6
AC Out Connection:
Select AC Load 1 to 10
AC1 Connection:
Select Grid 1 to 10,
Gen 1 to 10
AC2 Connection:
Select Grid 1 to 10,
Gen 1 to 10
XW_Operation.book Page 46 Wednesday, August 12, 2015 2:39 PM