Specifications Sheet
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Dec 20, 2012
1
Product data sheet
Characteristics
865-1010
Conext XW - inverter / charger
XW4024-120/240-60 - input: 178A DC
Main
Range of product XW
Device short name XW4024-120/240-60
Product or component
type
Hybrid inverter / charger
Network number of
phases
Single phase
Type of signal True sine wave
Continuous power 4000 W - 120 V AC (tolerance: +/- 3 %)
4000 W - 240 V AC (tolerance: +/- 3 %)
Complementary
Feature available 35 A for phase to phase (L-L), duration : 20 s
70 A for phase to neutral (L-N), duration : 20 s
Network frequency 60 Hz +/- 0.1 Hz (output)
Cos phi 0.98
Harmonic distortion < 5 %
Input voltage 25.2 V DC
240 V AC (L-L) - bypass/charge mode
120 V AC (L-N) - bypass/charge mode
Input voltage limits 22...32 V DC
214...260 V +/- 3.0 V AC (L-L) - sell mode
108...130 V +/- 1.5 V AC (L-N) - sell mode
160...270 V AC (L-L) - bypass/charge mode
80...150 V AC (L-N) - bypass/charge mode
Input current 178 A DC at rated power
Input frequency 44...70 Hz - bypass/charge mode (allowable)
55...65 Hz - bypass/charge mode (default)
59.4...60.4 Hz +/- 0.05 Hz - sell mode
Charging current 150 A
Efficiency 85.8 % - maximum charge rate
91 % CEC weighted
94 % - low-load
Power consumption in W < 8 W - search mode
Communication network type Xanbus
Device mounting Wall mounted
Provided equipment Battery temperature sensor included for temperature compensation
Height 580 mm
Width 410 mm
Depth 230 mm
Product weight 52.5 kg
Environment
NEMA degree of protection NEMA Type 1
Ambient air temperature for operation -25...70 °C
Standards CSA 107.1
UL 1741
Product certifications FCC Class B