Edition: 12 / 00
Multimode Relay MT
2 / 3 pole 10 A, DC- or AC-coil
Contact data
Configuration 2 C/O contact or 3 C/O contact
Type of contact single contacts bifurcated contacts
Rated current 10 A 4 A
Rated voltage / max.breaking voltage AC 250 Vac / 440 Vac
Maximum breaking capacity AC 2500 VA 500 VA
Make current (max. 4 s at duty cycle 10%) 20 A 8 A
Contact material AgNi 90/10
Minimum contact load
24 V, 10 mA / 20 mV, 1 mA gold plated
· 2 C/O or 3 C/O contacts
· Cadmium-free contacts
· DC and AC coils
· Mechanical indicator as standard
· Electrical indicator
· New test system with front operated finger protected
push-to-test button and integral locking test tab
· White write on panel
Applications
Mechanical engineering, plant control
VUCs
Technical data of approved types on request
Contact life
Type Load Operations Standard
MT321 10 A, 250 Vac, C/O contact 1x10
5
VDE 0435
Coil data
Nominal voltage DC coil 6...220 Vdc
AC coil 6...230 Vac
Nominal coil power DC coil typ. 1.2 W
AC coil typ. 2.3 VA
Operate category 1 / a
Coil versions, DC-coil
Coil code Nominal Pull-in Release Coil Coil
standard PD
*
voltage voltage voltage resistance current
Vdc Vdc Vdc c mA
006 0A6 6 4.5 0.6 32+10% 187.5
012 0B2 12 9.0 1.2 110+10% 109.1
024 0C4 24 18.0 2.4 475
++
10% 50.5
048 0E8 48 36.0 4.8 2000+10% 24.0
060 0G0 60 45.0 6.0 2850+10% 21.1
110 1B0 110 82.5 11.5 10000+12% 11.0
220 2C0 220 165.0 22.0 40000+15% 5.5
All figures are given for coil without preenergization, at ambient temperature +20°C
*
Protection diode PD; standard polarity: 2-pole relays: +2 / -7,
3-pole relays: +2 / -10
F0161-A