Setting point:
In this example, we ignore HIST. setting
Discharge: 47
0
F
Temp rise: 10
0
F
Water temperature reading:
Discharge: 60
0
F
Return #1: 63
0
F
Again, stage 1 is activated since discharge temperature reading is above discharge temperature
setting. This time stage 2 is also activated. The discharge temperature reading is 60
0
F, which is
above the sum of the discharge setting and temp rise setting (47+10 = 57).