Datasheet

1
Power Entry Modules with Line Filter
C20F
www.schurter.com/PG06
Connectors
IEC Appliance Inlet C20 with Filter, Front or Rear Side Mounting
Screw-on mounting
from front side
Snap-in mounting
from front side
Screw-on mounting
from rear side
with wires (stranded)
Standard- or Medical-Filter
C20
70° C
Description
- Panel Mount:
Screw-on version from front or rear side, snap-in version from front
side
- 2 Functions:
Appliance Inlet Protection class I, Line filter in standard and medical
version
- Solder, quick connect or wires (stranded)
Approvals
- VDE Certificate Number: 104884
- UL File Number: E72928
Characteristics
- Compact design with optimal shielding
Suitable for assembly in metal plated plastic housings
- Version with class X1 and X2 (standard version) capacitors
- Universal line filter for standard applications
Designed for standard and medical applications
- Suitable for use in equipment according to IEC 60950
Other versions on request
- 16A according to UL
- Capacity CX 330 nF
References
Alternative: Standard version
Alternative: version without line filter
4793
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, Mating Connectors,
e-Shop, SCHURTER-Stock-Check, Distributor-Stock-Check, CAD-
Drawings, Accessories, Wire Harnessing, Mounting instruction, Detailed
request for produc
t
Newly available variants corresponding to V-Lock mating cordset. The connector is equipped with a notch intended for use with the latching cordset.
The cord latching system prevents against accidental removal of the cordset.
Technical Data
Ratings IEC 16 A @ Ta 40 °C / 250 VAC; 50 Hz
Ratings UL/CSA 20 A @ Ta 40 °C / 250 VAC; 60 Hz
Leakage Current standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
Dielectric Strength > 1.7 kVDC between L-N (Cy2)
> 2.7 kVDC between L/N-PE (Cy2)
Test voltage (2 sec)
Impulse Withstand Voltage > 2.5 kV between L-N (CX2)
> 4 kV between L-N (CX1)
> 5 kV between L/N-PE (Cy2)
voltage (1.2/50 μs)
Allowable Operation Temp. -25 °C to 85 °C
Climatic Category 25/085/21 acc. to IEC 60068-1
Degree of Protection from front side IP 40 acc. to IEC 60529
Protection Class Suitable for appliances with protection
class I acc. to IEC 61140
Terminal Solder, quick connect or wires (stran-
ded)
Panel Thickness s Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Snap-in: 1 mm to 3 mm
Material: Housing Thermoplastic, black, UL 94V-0
Appliance-Inlet/-Outlet C20 acc. to IEC 60320,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 16 A,
Protection Class I
Line Filter Standard and Medical Version, IEC
60939, IEC 60601-1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical Details
MTBF > 3'000'000 h acc. to MIL-HB-217 F

Summary of content (5 pages)