Datasheet
Table Of Contents

1
Power Entry Modules with Line Filter
C20F
https://www.schurter.com /PG06
EMC Products
IEC Appliance Inlet C20 with Filter, Front or Rear Side Mounting
Screw-on mounting
from front side
Snap-in mounting
from front side
Screw-on mounting
from rear side
with wires (stranded)
See below:
Approvals and Compliances
C20
70° C
Description
- Panel mount :
Screw-on version from front or rear side, snap-in version from front
side
- 2 Functions :
Appliance Inlet Protection class I , Line filter in standard and medical
version
- Solder, quick connect or wires (stranded)
Unique Selling Proposition
- Attractive flat front design
- Highly resistant since fully potted
- Various filter variants
- V-Lock cord retaining
Characteristics
- Compact design with optimal shielding
Suitable for assembly in metal plated plastic housings
- Version with class X1 and X2 (standard version) capacitors
- Universal line filter for standard applications
- Suitable for use in equipment according to IEC/UL 60950
Suitable for use in medical equipment according to IEC/UL 60601-1
Other versions on request
- 16A according to UL
- Capacity CX 330 nF
References
Alternative: version without line filter 4793; 4798
Weblinks
pdf datasheet, html-datasheet, General Product Information, Distributor-
Stock-Check, Accessories, Detailed request for product, Microsite
Newly available variants corresponding to V-Lock mating cordset. The connector is equipped with a notch intended for use with the latching cordset.
The cord latching system prevents against accidental removal of the cordset.
Technical Data
Ratings IEC 16 A @ Ta 40 °C / 250 VAC; 50 Hz
Ratings UL/CSA 20 A @ Ta 40 °C / 250 VAC; 60 Hz
Leakage Current standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
Dielectric Strength > 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
Impulse Withstand Voltage > 2.5 kV between L-N (CX2)
> 4 kV between L-N (CX1)
> 5 kV between L/N-PE (Cy2)
voltage (1.2/50 μs)
Allowable Operation Tempe-
rature
-25 °C to 85 °C
Climatic Category 25/085/21 acc. to IEC 60068-1
IP-Protection from front side IP 40 acc. to IEC 60529
Protection Class Suitable for appliances with protection
class I acc. to IEC 61140
Terminal Solder, quick connect or wires (stran-
ded)
Panel Thickness S Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Snap-in: 1 mm to 3 mm
Material: Housing Thermoplastic, black, UL 94V-0
appliance inlet/-outlet C20 acc. to IEC 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 16 A,
Protection Class I
Line Filter Standard and Medical Version, IEC
60939, UL 1283, CSA C22.2 no. 8
Technical Details
MTBF > 3'000'000 h acc. to MIL-HB-217 F
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about
Approvals