Datasheet

1
Power Entry Modules with Line Filter
DD22
www.schurter.com/PG06
Connectors
IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole, Line Switch 2-pole, for PCB Mounting
Fuse drawer must be ordered separately (see
accessories).
Standard- or Medical-Filter
C14
70° C
Description
- Panel Mount:
Screw-on mounting on PCB, from rear-side
- 4 Functions:
Appliance Inlet Protection class I, Line Switch 2-pole, Fuseholder for
fuse-links 5 x 20 mm 1- or 2-pole, Line filter in standard and medical
version
- PCB solder terminals
Approvals
- VDE Certificate Number: 40001522
- UL File Number: E72928
Characteristics
- Ultra-compact design. Ideal for low profile designs
- All single elements are already wired
- For added safety "Extra-Safe" fuse drawers are available
Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuse drawer can only be opened with the aid of a tool
The fuseholder is accessible from the equipment front
- Ideal for application with high transient loads
- Suitable for use in equipment according to IEC 60950
Other versions on request
- Fuse drawer 1-pole, plus spare fuse case
- Fuse drawer 2-pole, with shorting bar
- Other rocker marking
- Line switch, illuminated
- Line switch 1-pole
- Medical version M80
- Protection class II, 70°C
References
Alternative: version without line filter DD21
Alternative: Standard version
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformit
y, RoHS, CHINA-RoHS, Mating Connectors,
e-Shop, SCHURTER-Stock-Check, Distributor-Stock-Check, CAD-
Drawings, Accessories, Mounting instruction, Detailed request for
product
Technical Data
Ratings IEC 1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
Ratings UL/CSA 1 - 10 A @ Ta 40 °C / 250 VAC; 50/60 Hz
Leakage Current standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
Dielectric Strength > 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (1 min/50 Hz)
Allowable Operation Temp. -25 °C to 85 °C
Climatic Category 25/085/21 acc. to IEC 60068-1
Degree of Protection from front side IP 40 acc. to IEC 60529
Protection Class Suitable for appliances with protection
class I acc. to IEC 61140
Terminal For PCB mounting 3 mm additional
quick connect 6.3 x 0.8 mm
Panel Thickness s Screw-on mounting: max 3 mm
Mounting screw torque max 0.5 Nm
Material: Housing Thermoplastic, black, UL 94V-0
Appliance-Inlet/-Outlet C14 acc. to IEC 60320
UL 498 CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class I
Fuseholder 1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 mm
Rated Power Acceptance @
Ta 23 °C
5 x 20: 2 W (1 pole)/ 1.6 W (2-pole) per
pole
Power Acceptance @ Ta >
23°C
Admissible power acceptance at hig
-
her ambient temperature see derating
curves
Line Switch Rocker switch 2-pole, non-illuminated,
acc. to IEC 61058-1
Technical Details
Line Filter Standard and Medical Version, IEC
60939, IEC 60601-1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical Details
MTBF > 2'000'000 h acc. to MIL-HB-217 F

Summary of content (5 pages)