Datasheet

1
Power entry modules without line filter
KM
www.schurter.com/PG05
Connectors
IEC Appliance Inlet C14 with Fuseholder 2-pole, Line Switch 1- or 2-pole
Snap-In Version KM with shield
Plug removal necessary for fuse
replacement
C14
70° C
Description
- Panel Mount:
Snap-in version from front side
- 3 Functions:
Appliance Inlet Protection class I, Line Switch 2-pole, Fuseholder for
fuse-links 5 x 20 mm 1- or 2-pole
- Quick connect terminals 4.8 x 0.8 mm
- With cover on rear-side
Approvals
- VDE Certificate Number: 40021981
- UL File Number: E93617
Characteristics
- Ultra-compact design. Small dimensions in front of and behind the pa-
nel
- All single elements are already wired
- For added safety "Extra-Safe" fuse drawers are available
Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuse drawer can only be opened with the aid of a tool
The fuseholder is accessible from the equipment front
- Ideal for application with high transient loads
- Suitable for use in equipment according to IEC 60950
Other versions on request
- Fuse drawer 1-pole, plus spare fuse case
- Fuse drawer 2-pole, with shorting bar
- Line switch 1-pole
- Other rocker marking
- Protection class II, 70°C
References
Alternative: version with line filter KMF
Alternative: version for screw mounting
DD11
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, Mating Connectors,
e-Shop, SCHURTER-Stock-Check, Distributor-Stock-Check, CAD-
Drawings, Accessories, Wire Harnessing, Mounting instruction, Detailed
request for produc
t
Technical Data
Ratings IEC 10 A / 250 VAC; 50 Hz
Ratings UL/CSA 10 A / 250 VAC; 60 Hz
Dielectric Strength > 2.5 kVAC between L-N
> 3 kVAC between L/N-PE
(1 min/50 Hz)
Allowable Operation Temp. -25 °C to 70 °C
Degree of Protection from front side IP 40 acc. to IEC 60529
Protection Class Suitable for appliances with protection
class I acc. to IEC 61140
Terminal Quick connect terminals 4.8 x 0.8 mm
, tin-plated
Panel Thickness s Snap-in: 1/1.5/2/2.5 mm
(all steps with one variant)
Material: Housing Thermoplastic, black, UL 94V-0
Appliance Inlet C14 acc. to IEC 60320,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class I
Fuseholder 1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 mm
Rated Power Acceptance @
Ta 23 °C
5 x 20: 2 W (1 pole)/ 1.4 W (2-pole) per
pole
Choose fuse-links for 2-pole version
in such a way that the typical power
acceptance is less than 1.4 W for each
pole
Power Acceptance @ Ta >
23°C
Admissible power acceptance at hig-
her ambient temperature see derating
curves
Line Switch Rocker switch 2-pole, non-illuminated,
acc. to IEC 61058-1
Technical Details

Summary of content (4 pages)