TO BE COMPLETED BY THE LICENSED INSTALLER:
HIGH INTENSITY COMMISSIONING REPORT
TYPE OF GAS: NG LP
DOES BUILDING HAVE A NEGATIVE CONDITION: YES NO
WILL HEATER BE EXPOSED TO WELDING FUMES: YES NO
IS HEATER EXPOSED TO CHEMICAL OR CORROSIVE ATMOSPHERE: YES NO
IS AN OPEN FLAME COMPATIBLE WITH THE INSTALLED LOCATION: YES NO
MINIMUM CLEARANCES CONFORM AS PER I&O MANUAL: YES NO
IF THIS IS A HIGH ALTITUDE AREA WHAT IS THE ALTITUDE ABOVE SEA LEVEL
IS HEATER SHORT AXIS HORIZONTAL WITH THE VENTURI ON TOP: YES NO
IS HEATER INTERLOCKED WITH AN EXHAUST FAN SYSTEM: YES NO
IS FAN SYSTEM 3 CFM PER 1000Btu/hr OF THE TOTAL HEAT LOAD: YES NO
WILL HEATER BE AFFECTED BY OVERHEAD CRANES / VIBRATION: YES NO
IS GAS SUPPLY LINE ADEQUATELY SIZED FOR SYSTEM VOLUME: YES NO
HAVE GAS LINES AND BRANCHES BEEN PURGED OF AIR: YES NO
THIS HEATER WAS FIELD TEST FIRED WITHOUT ANY MALFUNCTION: YES NO
INLET GAS SUPPLY PRESSURE WITH HEATER OPERATING: WC"
GAS VALVE OUTLET (Manifold) PRESSURE WITH HEATER OPERATING: WC"
HAS THE WIRING POLARITY BEEN MAINTAINED THROUGHOUT: YES NO
WHAT IS THE VOLTAGE READING AT THE IGNITION MODULE: VOLTS
WHAT IS THE FLAME SIGNAL STRENGTH IN uA FROM SENSOR: uA (microamps)
IS THE HEATER CONTROLLED BY A THERMOSTAT: YES NO
IS THE THERMOSTAT STRATEGICALY LOCATED: YES NO
TOTAL HEATERS SUPPLIED FROM ONE SINGLE TRANSFORMER: TOTAL
WHAT IS THE RATING OF THE TRANSFORMER IN VA: V.A.
WHAT IS THE TOTAL LENGTH OF THE LOW VOLTAGE WIRING: FEET
WHAT IS THE GAUGE OF THE LOW VOLTAGE WIRING: GAUGE
THIS HEATER MUST HAVE GOOD ELECTRICAL GROUNDING:
* FAX COMPLETED FORM TO TECHNICAL SERVICES: CANADA - 905-712-8336 USA - 706-554-9390
Feet
1-866-361-0523
LUMINOUS HEATER COMMISSIONING REPORT
IS HEATER LONG AXIS HORIZONTAL (LEVEL)
IS FAN SYSTEM CAPACITY (4 cfm /1000 Btuh USA; 300 cfm / 100,000 Btuh
Canada) CORRECT FOR THE TOTAL HEAT LOAD: