INSTALLATION / OWNER’S MANUAL ECOSCHWANK 36-52 IL 150-200 SERIES LUMINOUS GAS FIRED INFRA RED HEATERS FOR YOUR SAFETY: FIELD CONVERTIBILITY: Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance.
NOTICE: The manufacturer reserves the right to make changes to equipment and specifications without obligation or notification. This publication, or parts thereof, may not be reproduced in any form, without prior written consent from the manufacturer. Unauthorized use or distribution of this publication is strictly prohibited. Schwank Inc. 5285 Bradco Boulevard, Mississauga, Ontario, phone: (905) 712-4766 fax: (905) 712-8336 1-866-361-0417 InfraSave Inc.
ECOSCHWANK 36-52 / IL150-200 LUMINOUS SERIES INFRA-RED GAS TUBE HEATERS TABLE OF CONTENTS TOPIC PAGE NUMBER 1. GENERAL .................................................................1 2. INSTALLATION REQUIREMENTS ........................1 2.1 INSTALLATION IN AIRCRAFT HANGARS ....1 2.2 INSTALLATION IN COMMERCIAL GARAGES ............................................................1 2.3 INSTALLATIONS OTHER THAN SPACE HEATING ...............................................................1 2.
SP-MEC3-BX-09A ecoSchwank 36-52 / IL 150-200 Manual RD: Sept, 2005 RL: 9 KH
ECOSCHWANK 36-52 / IL 150-200 INSTALLATION INSTRUCTIONS 1. GENERAL The gas fired infra-red luminous heaters are suitable to be installed for heating of non-residential indoor or outdoor spaces. Installation of the ecoSchwank 36-52 / IL 150-200 Series heaters must conform to all Schwank heating installation design procedures including ventilation. All local, provincial and national code requirements including the current latest edition B149.1-00 INSTALLATION CODE” in Canada, and ANSI Z223.1 in the U.S.A.
2.4 MOUNTING CLEARANCES The ecoSchwank 36-52 / IL 150-200 Luminous Heater must be mounted with minimum clearances as shown in sections 9.3. It should also be located with respect to building construction and equipment so as to provide sufficient clearance and accessibility for servicing and cleaning of burners and ignition control. WARNING: Luminous Heaters cannot be installed inside degreasing plants, nor can they be in an area where chlorine, fluorine or bromine are present. 2.
2.8 GAS PRESSURE The maximum supply pressure must be limited to 14" W.C. (0.51 psi). If the line pressure is above 14" W.C., then a separate pressure reducing regulator must be used. The minimum pressure at the inlet to the heater regulator must be equal to or greater than 6.0" W.C. for natural gas and 11.0" W.C. for propane gas.
3. HIGH ALTITUDE INSTALLATIONS Canada: All Luminous heaters are approved for altitudes zero to 2000 ft above sea level. If installed at 2000 ft to 4500 ft above sea level the heater must be ordered as High altitude. Contact Technical Services at 1-866-361-0417 for further information. USA: If a heater is to be installed at altitudes above 2000 ft, the input must be reduced by 4% per 1000 ft.
4.1 VENTURI AND GAS VALVE ASSEMBLY 1. Remove valve and heater from carton. Remove the three screws from each venturi collector bell located on one end of the heater. 2. Slide valve onto collector bells and insert two vertical screws. Then install remaining four screws. 3. To avoid possible damage to wiring connection, it may be advantageous to hang heater before connecting wires. Connect two gray wires to the flame sensors located by the electrodes.
5. LIGHTING INSTRUCTIONS A Open the isolation valve in the main gas line and turn gas control knob on the combination gas valve to the “ON” position. B Switch on electrical circuit by turning the thermostat to the highest temperature setting. C The heater should attempt ignition and remain lit within thirty seconds. Note that the corresponding exhaust fan is operating properly. D If ignition does not occur, then cut off electrical power by turning the thermostat to off position.
9. DIAGRAMS AND SPECIFICATIONS: 9.1 DIMENSIONS FOR THE LUMINOUS HEATERS A C 9 1/4” 8 1/2” B MODEL N0. A B C RATING BTU/HR WEIGHT LBS. ecoSchwank 36 36 3/4” 48 1/2” 20” 150,000 60 ecoSchwank 52 53 1/4” 63 3/4” 20” 200,000 70 9.
9.3 MINIMUM CLEARANCE TO COMBUSTIBLES FRONT A A E A 300 SIDE END B B END D D F D HORIZONTAL MOUNT Series ANGLE MOUNT 36 / 150N/L 52 / 200N/L Top of Heater (A) 52” 52” Sides of Heater (B) 55” 55” End of Heater (C) 39” 39” Bottom of Heater (D) 121” 121” 9.
10. TROUBLE SHOOTING GUIDE SERVICE HINTS AND MAINTENANCE CAUSE AND CORRECTIONS TURN THERMOSTAT TO CALL FOR HEAT CHECK FOR LINE VOLTAGE POWER SUPPLY NO YES 24 VOLTS AT CONTROL TRANSFORMER YES NO 24 VOLT AT CONTROL REPLACE TRANSFORMER CHECK 24V WIRING FROM TRANSFORMER TO IGNITION CONTROL NO YES REPLACE CONTROL 24 VOLTS OUT CONTROL YES NO CHECK 24V WIRING FROM IGNITION CONTROL TO GAS VALVE NO PULL IGNITION LEAD AND CHECK SPARK AT IGNITION STUD.
11.
12. SPARK IGNITION SYSTEM INFORMATION: OPERATION Upon applying power (24VAC) to 24V terminal, the control will reset, perform a self check routine, initiate full time flame sensing, flash the diagnostic LED for up to four seconds, and enter the thermostat scan state. HEAT MODE When a call for heat is received from the thermostat 24 volts is supplied to TH/W, a pre-purge delay begins, then the gas valve is energized and the sparks commence at both burners for the trial for ignition period.
13. START UP SHEET AS PER I&O MANUAL AND LOCAL CODES CONTRACTOR NAME: ................................................................................DATE................................ ADDRESS:............................................................................................................................................ ............................................................................................................................................................ CITY:............
TO BE COMPLETED BY THE LICENSED INSTALLER: HIGH INTENSITY COMMISSIONING REPORT TYPE OF GAS: NG LP DOES BUILDING HAVE A NEGATIVE CONDITION: YES NO WILL HEATER BE EXPOSED TO WELDING FUMES: YES NO IS HEATER EXPOSED TO CHEMICAL OR CORROSIVE ATMOSPHERE: YES NO IS AN OPEN FLAME COMPATIBLE WITH THE INSTALLED LOCATION: YES NO MINIMUM CLEARANCES CONFORM AS PER I&O MANUAL: YES NO IF THIS IS A HIGH ALTITUDE AREA WHAT IS THE ALTITUDE ABOVE SEA LEVEL Feet IS HEATER SHORT AXIS HORIZONTAL WITH THE VENT
SP-MEC3-BX-09A ecoSchwank 36-52 / IL 150-200 Manual RD: Sept, 2005 RL: 9 KH
LIMITED WARRANTY CERTIFICATE GAS-FIRED INFRA-RED LUMINOUS SERIES: ECOSCHWANK / IL SERIES The Manufacturer warrants that this product is free from defects in material or workmanship under normal use and service subject to the terms of this document.