NOTICE: Schwank Inc., reserves the right to make changes to equipment and specifications without obligation or notification. All codes are current at the time of printing. This publication, or parts thereof, may not be reproduced in any form, without prior written consent from Schwank Inc. Unauthorized use or distribution of this publication is strictly prohibited. Schwank Inc. 5285 Bradco Boulevard Mississauga, Ontario, L4W 2A6 phone: (905) 712-4766 fax: (905) 712-8336 Schwank Inc.
SCHWANK GAS INFRA-RED TUBE HEATER STS-p SERIES INSTALLATION INSTRUCTIONS TABLE OF CONTENTS TOPIC PAGE NUMBER 1. GENERAL..................................................1 2. INSTALLATION IN AIRCRAFT HANGARS.................................................1 2.1 INSTALLATION IN COMMERCIAL GARAGES ..................................................1 3. INSTALLATIONS OTHER THAN SPACE HEATING.....................................1 4. HEATERS AND TUBE KITS...................2 TUBE KIT MATRIX.....................
SP-MSTP-AC-15A STS-p Manual RD: DEC, 2003 RL:15 KH
SCHWANK GAS INFRA-RED TUBE HEATER STS-P SERIES INSTALLATION INSTRUCTIONS 1. GENERAL Installation of the Schwank STS-p Series gas-fired tube heaters must conform to all Schwank heating installation design procedures including ventilation. All local, provincial and national code requirements including the current latest edition B149.1 INSTALLATION CODE” in Canada, and ANSI Z223.1 in the U.S.A. for gas burning appliances and equipment. The latest edition Electrical Code PART 1 CSA C22.
4.
STSp HEATER KIT Order STSp TUBE KIT PART # & QUANTITY REQUIRED ASSEMBLY CHART Stand-Alone Kits Order HEATER MODEL BURNER KIT STSp 45 10 JS-S045-B N/L STSp 45 20 JS-S045-B N/L STSp 60 20 JS-S060-B N/L STSp 60 30 JS-S060-B N/L STSp 80 20 JS-S080-B N/L STSp 80 30 JS-S080-B N/L STSp 80 40 JS-S080-B N/L STSp 110 30 JS-S110-B N/L STSp 110 40 JS-S110-B N/L STSp 110 50 JS-S110-B N/L STSp 130 30 JS-S130-B N/L STSp 130 40 JS-S130-B N/L STSp 130 50 JS-S130-B N/L STSp 155 40 JS-S155-B N
5. PRE-INSTALLATION SURVEY The Schwank STS-p heating system must have gas piping of the correct diameter, length, and arrangement to function properly. For this reason, a layout drawing is necessary. Carefully survey area to be heated, and for best results, whenever possible, place burner and combustion chamber in coldest area. 6. MOUNTING CLEARANCES This heater must be mounted with at least minimum clearances between the reflector surface and combustibles as shown in FIGURE 1, TABLE 3, ON PAGE 5.
FIGURE 1 MINIMUM CLEARANCES TO COMBUSTIBLES TABLE 3 MINIMUM CLEARANCES TO COMBUSTIBLES SUSPENDED AT AN ANGLE UP TO 45 DEGREES MODEL SUSPENDED HORIZONTALLY D E F G A B C STS-p 200 7” 1” 57” 68” 7” 22” 68” STS-p 175 6.5” 1” 47” 68” 6.5” 20” 68” STS-p 155 6” 1” 44” 64” 6” 19” 64” STS-p 130 5” 1” 35” 56” 4” 11” 60” STS-p 110 4.5” 1” 26” 54” 4” 10” 54” STS-p 80 3.5” 1” 23” 38” 2.5” 6” 36” STS-p 60 3” 1” 17” 34” 2.5” 5.
7. SYSTEMS INCORPORATING 90O ELBOWS AND 180O ELBOWS The STS-p Series radiant tube heater can be installed in configurations as illustrated in FIGURE 2. (below) with a maximum of two 90o or one 180o elbow per heater. The use of radiant elbows reduces the total maximum vent allowable. See SECTION 11 (PAGE 15): Re: Flue venting. Both the 90o and 180o elbows are shipped as a kit with one coupler and two end plate hangers to close off the reflector ends each side of the elbow (s).
8. SUSPENSION SYSTEM End plate hangers are provided to support reflectors and tubes at both ends of heater, that is at burner and at flue, see FIGURE 3 (below), FIGURES 4,5,6 (PAGE 8). Wire hangers are provided to support reflectors and tubes along the full length between the two end plate hangers, SEE FIGURES 4,5 (PAGE 8) and FIGURES 7,9 (PAGE 9). (The STS-p 45-10 DOES NOT require wire hangers, as the reflector is supported at both ends by the end plate hangers).
FIGURE 4 TYPICAL HANGER & SUPPORT SPACING RECOMMENDATIONS 4” 3" 11 4" 12 4 9 1 3 6 5 1 10 7 2 8 13 "ALL TUBES MUST BE SUSPENDED BY TWO (2) HANGERS PER 10' LENGTH, MOUNTED APPROXIMATELY 6" TO 12" IN FROM EACH TUBE END.
FIGURE 7 HANGER / REFLECTOR ORIENTATION HORIZONTAL TO 450 Side ring for angle mounting at 450 degrees Side ring for angle mounting at 450 degrees Top ring for horizontal mounting Using a 1800 elbow will adapt straight tubes into a horizontal or angled “U” tube system as illustrated above FIGURE 8 SUGGESTED MOUNTING HARDWARE E Y E SCREW EYE B O L T BEAM CLAMP THROUGH WITH EYE PIPE RING OR CLEVIS B A R - FIGURE 9 REFLECTOR STABILIZER Note: Use the reflector stabilizer for Reflector Stabilizer Reflec
9. BURNER AND TUBE INSTALLATION With all hangers suspended at the same height, insert first aluminized tube section, through 4" hole in first end plate hanger and onto wire hanger. End plate hanger should butt against the sight glass on the bottom of the tube, SEE FIGURE 4 (PAGE 8). Bolt burner to flange on first tube section, SEE FIGURE 10 (BELOW). Subsequent lengths of tube can then be installed, joining them together one inside the other.
TABLE 4 TURBULATOR LENGTH MODEL TURBULATOR LENGTH MODEL (IF REQUIRED) (IF REQUIRED) STS-p 200-70/60/50 10’ STS-p 110-40 10' STS-p 175-70/60/50 10’ STS-p 110-30 14' STS-p 155-60 not required STS-p 80-40 10’ STS-p 155-50 not required STS-p 80-30 14' STS-p 155-40 10' STS-p 80-20 14' STS-p 130-50 not required STS-p 60-30 14’ STS-p 130-40 10' STS-p 60-20 14' STS-p 130-30 14' STS-p 45-20 5’ STS-p 110-50 not required STS-p 45-10 5’ NOTE: Where required the STS-p Se
FIGURE 13 MOUNTING FOCUS SHIELD REFLECTOR TO END PLATE HANGER 1 7 2 2 4 1 3 5 4 5 1 6 7 3 End-Plate-Hanger Flange over the Reflector End-Plate-Hanger Flange under the Reflector Screws securing Reflector to End-Plate-Hanger Chain Hole for horizontal suspension Chain Hole for up to 45º suspension Opening for Tube Focus-Shield Reflector* 7 6 10.
NOTE: For angle mounted applications use the reflector stabilizer(s) See FIGURE 9 (PAGE 9) FIGURE 14 FOCUS SHIELD REFLECTOR SLIDE 1 2 Reflector 4 3 Reflector Slide 1 FIGURE 15 HANGER ARRANGEMENTS 1 ADDITIONAL TUBE(S) 3 2 4 FIRST TUBE 5 Page 13 1 Two Wire Hangers per Each Middle Section 2 Use End Plate Hangers at Burner & Flue Ends (& each side of any elbow) 3 End Plate Hanger Flange UNDER Focus Shield Reflector 4 End Plate Hanger Flange OVER Focus Shield Reflector 5 Butt Sight Glass Ring to End Pl
FIGURE 16 REFLECTOR EXTENSIONS (OPTIONAL - IF REQUIRED ) 10” 3 D View • • Page 14 Using “S” Hooks attach the two Reflectors.
11. FLUE VENTING NOTE: The STSp series is approved for both direct and indirect vented applications. The system must not be operated in a negative air condition, unless combustion air is brought in from outside directly to the burner. If a severe negative pressure is experienced or anticipated, order heater requesting custom Air Switch c/w Air Hose from Schwank. * Ensuring you specify the correct heater model number when ordering.
When venting horizontally, the flue vent system should slope downwards approximately 1/4" per foot toward the vent terminal, starting at the termination of the radiant tube. For horizontal through the wall venting, the approved Schwank 4" or 6" vent terminal should be used. Install the flue vent terminal 18" from the outside wall to the inside end of terminal opening. The flue vent terminal used must be of the approved types supplied by Schwank or supplied by an approved "B" vent manufacturer.
Where the vent pipe passes through areas where the ambient temperature is likely to produce condensation of the flue gases, t h e vent pipe shall be insulated with a suitable material as approved and specified by the insulation manufacturer. Check with Schwank Tech. Support as to the maximum vent temperature requirements. The vent system must always be adequately supported to prevent sagging.
For ease of installation, this heater has been provided with a fresh air intake duct hood. It can be used as an outdoor intake hood to bring combustion air to the heater from outside. Or to use air directly from the room, it must be installed over the intake flange on top of the burner. If drawing in fresh air from outside, it is recommended as per common Engineering practice, that the combustion air intake duct be insulated. Do not use flexible dryer hose for air inlet duct.
DO NOT use pressures greater than 1/2 psig. to pressure check the heater. TEST FOR LEAKS: All gas piping and connections must be tested for leaks after the installation is completed. Apply soap suds solution to all connections and joints and if bubbles appear, leaks have been detected and must be corrected. DO NOT USE A MATCH OR OPEN FLAME OF ANY KIND TO TEST FOR LEAKS. NEVER OPERATE THE HEATER WITH LEAKING CONNECTIONS.
14. HEATER EXPANSION Due to the characteristics of tube heaters, the installer must allow for 1” expansion for every 10’ length of tube. In order to address this characteristic, it is suggested that the gas line, flue vent, and combustion air intake (if used) shall be installed in such a manner, that the normal expansion of the heater will be accommodated.
15. ELECTRICAL AND THERMOSTAT WIRING (SEE WIRING DIAGRAMS PAGES 23, 26, 31) Wiring must be done in accordance with local codes. The total load of all heaters must be considered in determining the required contact rating of the controlling thermostat or switch. Each tube heater requires 120V, 60 HZ electrical power sized for 145VA. The heater can be controlled by the Schwank Tru-Temp Thermostat, a line voltage Thermostat or by an “ON/OFF" switch.
17. LIGHTING INSTRUCTIONS NOTE: Refer to the lighting instructions on the inside On initial installation, the unit cover of the burner housing. Again, if the may lock out on safety owing to unit goes off on safety, main power to the the length of time required to unit must be manually interrupted for a 30 bleed air from the gas piping second reset period before the heater can be system. restarted. 18. RECOMMENDED MAINTENANCE 1.
19. CA SERIES SEQUENCE OF OPERATION - HONEYWELL S87J-1034 CA Series: The STS-p Burner with direct spark ignition, sequence is as follows : 1. Upon a call for heat by the line voltage Thermostat or "ON/OFF" switch, the Blower and the 120/24 volt Transformer are powered simultaneously with 115 volts. 5. After completing the 30 second pre-purge cycle the DSI control generates high voltage to the Spark Igniter, and 24 volts to energize the Gas Valve. 1a.
STSp-CA SERIES: WIRING DIAGRAM - HONEYWELL S87J1034 WITH 120 V THERMOSTAT Page 24 SP-MSTP-AC-15A STS-p Manual RD: DEC, 2003 RL:15 KH
CA SERIES: TROUBLESHOOTING GUIDE HONEYWELL S87J1034 120V THERMOSTAT APPLY 115 VOLTS ON 24V OPTION ONLY: THE SWITCHING RELAY ENERGIZES, SENDING 115 VOLTS TO THE BLOWER SET THERMOSTAT TO CALL FOR HEAT CHECK IF 115 VOLTS PRESENT AT BLOWER IF SO............REPLACE DEFECTIVE BLOWER COMBUSTION AIR BLOWER STARTS NO ON 24V OPTION ONLY: CHECK FOR II5V FROM SWITCHING RELAY. CHECK 24V SIDE OF RELAY VOLTAGE. CHECK 115V LINE SIDE OF RELAY VOLTAGE. CHECK OPERATION OF BOTH CIRCUITS.
cont’d MAIN BURNER LIGHTS NO YES CHECK FOR GOOD SPARK AT IGNITER.....(SEE PREVIOUS PAGE) CHECK OUTPUT VOLTAGE FROM CONTROL TERMINALS....IF NONE REPLACE CONTROL. CHECK FOR 25 VAC ACROSS GAS VALVE. CHECK ELECTRICAL WIRING BETWEEN IGNTION CONTROL AND GAS VALVE.... IF OK, .........REPLACE GAS VALVE. CONTROL IS NOT SENSING FLAME WITHIN THE 21 SECOND TFI AND IS STILL TRYING TO LIGHT SPARK STOPS WHEN BURNER LIGHTS NO YES CHECK CONTINUITY OF SENSOR CABLE AND GROUND WIRE. CHECK BURNER FLAME IS COVERING SENSOR.
24 VOLT OPTION AVAILABLE : STSp-CA SERIES: WIRING DIAGRAM - HONEYWELL S87J1034 RELAY Page 27 SP-MSTP-AC-15A STS-p Manual RD: DEC, 2003 RL:15 KH
21. SPARK IGNITION CIRCUIT The step-up transformer in the ignition control provides spark ignition at 30,000 volts (open circuit). To check the spark ignition circuit, proceed as follows.
22. START-UP SHEET START UP SHEET INSTALLATION SET-UP AS PER IOM MANUAL AND LOCAL CODES CONTRACTOR NAME: .................................................................................................................. ADDRESS:........................................................................................................................... ................................................................................................................................... CITY:.....................
TO BE COMPLETED BY THE LICENSED INSTALLER: LOW INTENSITY START-UP TYPE OF GAS: NG LP DOES BUILDING HAVE A NEGATIVE CONDITION: YES NO IS THIS A HIGH ALTITUDE AREA - (OVER 2000 FT ABOVE SEA LEVEL) YES NO IF HIGH ALTITUDE W HAT IS THE ACTUAL ALTITUDE ABOVE SEA LEVEL FEET DOES ENVIRONMENT REQUIRE FRESH AIR TO BURNER YES NO IS HEATER EXPOSED TO CHEMICAL OR CORROSIVE ATMOSPHERE: YES NO MINIMUM CLEARANCES ARE AS RECOMMENDED IN TABLE 3 YES NO WILL HEATER BE AFFECTED BY OVERHEAD CRANES / VIBRATIO
23.
90 degree Aluminized Steel Elbow Kit* (*Kit includes: elbow, coupler, and two end plate hangers) JS-0508-SW 180 degree Aluminized Steel Elbow Kit* (*Kit includes: elbow, coupler, and two end plate hangers) JS-0513-SW Line Voltage Thermostat: Not to be used in corrosive or wet environments JL-0772-XX 10’ Tube & Reflector Extension Kit (1-10’ Steel Tube, l-l0’Reflector, 2 Wire Hangers, 1 Coupler, 1 Reflector Stabilizer, 1 Reflector Slide) TS-1010-CX Page 32 SP-MSTP-AC-15A STS-p Manual RD: DEC, 2003 R
TruTemp Thermostat (Do Not use in wet or corrosive environments) JM-0150-XX JS-0569-XX Low Voltage Thermostat (24 Volts) Not to be used in corrosive or wet environments 24 Volt Option: Single heater per Thermostat for field mounting in Burner housings (TruTemp or 24 Volt Thermostat extra). JS-0568-KT 24 Volt Option: Multiple Heaters per Thermostat JM-0303 –KT ( for field mounting.