INSTALLATION / OWNER’S MANUAL STW - JZ, STW-JZ-2 & IW SERIES Car Wash & Harsh Environment LOW INTENSITY TUBE TYPE INFRA RED HEATERS FOR YOUR SAFETY: FIELD CONVERTIBILITY: Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance.
NOTICE: The Manufacturer reserves the right to make changes to equipment and specifications without obligation or notification. This publication, or parts thereof, may not be reproduced in any form, without prior written consent from The Manufacturer. Unauthorized use or distribution of this publication is strictly prohibited. Schwank Inc. 5285 Bradco Boulevard Mississauga, Ontario, L4W 2A6 Phone: (905) 712-4766 Fax: (905) 712-8336 1-866-361-0417 InfraSave Inc.
Car Wash & Harsh Environment STW-JZ / IW HARSH ENVIRONMENT INFRA-RED GAS TUBE HEATERS TABLE OF CONTENTS TOPIC 1. 2.1 2.2 3. PAGE NUMBER GENERAL ............................................... 1 INSTALLATION IN CAR WASHES......... 1 INSTALLATION ON PATIOS....................1 INSTALLATIONS OTHER THAN SPACE HEATING ................................... 1 4. BURNER & TUBE KIT ASSEMBLY CHARTS .... 3 5. PRE-INSTALLATION SURVEY .............. 4 6. MOUNTING CLEARANCES ................... 4 7.
GP-MSJW-CX-07B STW-JZ / IW Manual RD: Sept, 2005 RL: 7B KH
GAS INFRA-RED TUBE HEATER STW-JZ / IW SERIES INSTALLATION INSTRUCTIONS 1. GENERAL Installation of the STW-JZ / IW Series gas-fired tube heaters must conform to all manufacturers heating installation design procedures including ventilation. All installations in Canada must conform to local and national code requirements including the current CSA-B149.1-00 installation code for gas burning appliances and equipment, and Canadian Electrical Code part 1 CSA C22.1 latest edition must be observed.
The following tube lengths and corresponding BTU/hr input ratings are available: CAUTION ! TABLE 1 MODELS AVAILABLE RECOMMENDED SIZES FOR STANDARD PATIO APPLICATIONS BTU/HR INPUT O’ TO 45OO’ ABOVE SEA LEVEL OVERALL HEATER LENGTH* (FT) APPROX.
4. BURNER & TUBE KIT ASSEMBLY CHARTS NOTE: STW-JZ / IW Series Burners require 120V supply—Now available with a 24V option Stand-Alone Tube Kits require no additional Tube Kits Primary Tube Kits require at least one additional Secondary Tube Kit Secondary Tube Kits require a Primary Tube Kit Secondary Tube Kit TW-1010-JZ can also be used as a 10ft extension kit. The installer may need to remove the turbulator (refer to Turbulator Chart in the I & O Manual.
5. PRE-INSTALLATION SURVEY The STW-JZ / IW heating system must have gas piping of the correct diameter, length, and arrangement to function properly. For this reason, a layout drawing is necessary. Carefully survey area to be heated. For best results, whenever possible, place burner and combustion chamber in coldest area. One side panel of the burner accommodates the gas and electrical connections into the burner making it much more difficult to remove.
FIGURE 1 MINIMUM CLEARANCES TO COMBUSTIBLES D A E B B F C G TABLE 3 MINIMUM CLEARANCES TO COMBUSTIBLES SUSPENDED AT AN ANGLE UP TO 45 DEGREES MODEL SUSPENDED HORIZONTALLY D E F G A B C STW-JZ / IW-200 6” 1” 57” 68” 6.5” 22” 68” STW-JZ / IW-175 4.5” 1” 47” 68” 5.5” 20” 68” STW-JZ / IW-155 3.5” 1” 44” 64” 5.5” 19” 64” STW-JZ / IW-130 3.3” 1” 35” 56” 4.5” 11” 60” STW-JZ / IW-110 2” 1” 26” 54” 3.5” 10” 54” STW-JZ / IW-80 1.75” 1” 23” 38” 3” 6.
7. SYSTEMS INCORPORATING 90O ELBOWS AND 180O ELBOWS The 90o elbows are shipped as a kit with one coupler, one reflector and one plate hanger, for 1800 elbows you must order 2 x 900 kits. An optional angle mounting elbow kit is also available and must be ordered with elbow kits. The Reflectors must be secured to each of the plate hangers, See FIG: 6 (PAGE 8). The STW-JZ / IW Series radiant tube heater can be installed in configurations as illustrated in FIGURE 2.
8. SUSPENSION SYSTEM 1) Survey the available structural supports, considering the system configuration and heat requirements of the area to establish the optimum heater location.
FIGURE 4 TYPICAL HANGER & SUPPORT SPACING RECOMMENDATIONS 1. 2. 3. 4. 5. 6. 7. 8. 9. Burner Assembly Flange Adapter Flanged Tube Swaged Tube Flue Vent Terminal End Plate Hanger Webbed Hanger Hanging Chains Focus Shield Reflector FIGURE 5 REFLECTOR STABILIZER FIGURE 6 PLATE HANGER/ELBOW INSTALLATION 4 2 4 6 3 6 5 1 5 3 2 JS-0508-JZ 1. Webbed-Hanger 2. Reflectors 3. Webbed-Hanger Flange UNDER Reflector 4. Webbed Hanger Flange to mount UNDER the next Reflector 5. 900 Elbow (shown) 6.
FIGURE 7 HANGER / REFLECTOR ORIENTATION HORIZONTAL TO 450 Top ring for horizontal mounting Side ring for angle mounting at 450 degrees Side ring for angle mounting at 450 degrees Using 2 x 900 elbows will transform straight tubes into a horizontal or angled “U” tube system as illustrated below RETURN IS ON TOP BURNER MUST BE LOWER THAN VENT FIGURE 8 SUGGESTED MOUNTING HARDWARE EYE BOLT THROUGH HOLE IN BEAM BEAM CLAMP WITH EYE SCREW EYE SCREW Page 9 PIPE RING OR CLEVIS HANGER BARJOIST GP-MSJW-C
9. BURNER AND TUBE INSTALLATION PRIOR TO PROCEEDING with the tube installation: Refer to section “8.
b) Adjust the hanger so that it is located on the second tube, approximately 2” from the end of the tube – in this location the hanger supports both tubes.
TABLE 4 TURBULATORS MODEL TURBULATOR LENGTH (IF REQUIRED) MODEL TURBULATOR LENGTH (IF REQUIRED) STW-JZ / IW-200-70/60/50 10’ STW-JZ / IW-110-40 10’ STW-JZ / IW-175-70/60/50 10’ STW-JZ / IW-110-30 14’ STW-JZ / IW-155-60 not required STW-JZ / IW-80-40 10’ STW-JZ / IW-155-50 not required STW-JZ / IW-80-30 14’ STW-JZ / IW-155-40 10’ STW-JZ / IW-80-20 14’ STW-JZ / IW-130-50 not required STW-JZ / IW-60-30 14’ STW-JZ / IW-130-40 10’ STW-JZ / IW-60-20 14’ STW-JZ / IW-130-30 14’ STW
FIGURE 13 MOUNTING FOCUS SHIELD REFLECTOR TO PLATE HANGER 1 2 3 4 Webbed Hanger Flange under Reflector Screws to secure Reflector to Plate Hanger. Chain Hole for horizontal suspension Chain Hole for 45° suspension 5 Opening for Tube 6 Reflector 7 The following Reflector will mount over and onto this side of the Webbed Hanger. NOTE: For suspension between 1° and 44°, use both suspension points 3 and 4 (see details Fig.15 on Page 13). 10.
FIGURE 15 HANGER ARRANGEMENTS NOTE: Except for the vent end plate hanger, all hangers must be installed with the cavity side facing the burner end of the system - the cavity side of the vent end hanger must face the vent 1 1 Page Page 13 14 GP-MSJW-CX-07B STW-JZ / IW Manual RD: Sept, 2005 RL: 7B KH
FIGURE 16 REFLECTOR EXTENSIONS (OPTIONAL - IF REQUIRED ) 10” • • Using “S” Hooks attach the two Reflectors.
11. FLUE VENTING THIS STW-JZ / IW SERIES IS APPROVED FOR BOTH DIRECT AND INDIRECT VENTING APPLICATIONS. THE SYSTEM MUST NOT BE OPERATED WITHIN A NEGATIVE AIR CONDITION, UNLESS COMBUSTION AIR IS BROUGHT IN FROM OUTSIDE DIRECTLY TO THE BURNER (COMBUSTION AIR IS A REQUIREMENT FOR CAR WASH INSTALLATIONS).
The heater is designed to operate with single wall 4” diameter 26 gauge minimum exhaust vent. When vent and combustion air are taken through the roof, the exhaust vent should always terminate higher than the combustion air intake, to prevent recycling the products of combustion back into the heater. FIGURE 17 The total maximum allowable combined length of vent and combustion air duct is 80' for STW-JZ / IW 200, 175, 155 and 130, and 50' for STW-JZ / IW 110, 80, 60 and 45.
Where the vent pipe passes through areas where the ambient temperature is likely to produce condensation of the flue gases, the vent pipe shall be insulated with a suitable material as approved and specified by the insulation manufacturer. Check with the manufacturers Technical Support as to the maximum vent temperature requirements. The vent system must always be adequately supported to prevent sagging.
Do not install filters on the combustion air intake. For ease of installation, this heater has an optional fresh air intake duct hood. It can be used as an outdoor intake hood to bring combustion air to the heater from outside. If drawing in fresh air from outside, it is recommended as per common Engineering practice, that any single wall pipe exposed to cold air must be insulated to prevent condensation.
DO NOT use pressures greater than 1/2 psig. to pressure check the heater. TEST FOR LEAKS: All gas piping and connections must be tested for leaks after the installation is completed. Apply soap suds solution to all connections and joints and if bubbles appear, leaks have been detected and must be corrected. DO NOT USE A MATCH OR OPEN FLAME OF ANY KIND TO TEST FOR LEAKS. NEVER OPERATE THE HEATER WITH LEAKING CONNECTIONS.
14. HEATER EXPANSION The Btu/hr input and the tube length determine the overall expansion that occurs in a tube system. A typical infrared tube installation will expand toward both the Burner and the vent end. In order to address this issue it is suggested that the gas line, flue vent, and combustion air intake (if used) shall be installed in such a manner that the normal expansion of the heater will be accommodated.
15. ELECTRICAL AND THERMOSTAT WIRING (SEE WIRING DIAGRAMS PAGES 23, 26) Wiring must be done in accordance with local codes. The total load of all heaters must be considered in determining the required contact rating of the controlling thermostat or switch. Each tube heater requires 120V, 60 HZ electrical power sized for 145VA. The heater can be controlled by the TruTemp Thermostat, a line voltage Thermostat or by an “ON/OFF" switch.
17. LIGHTING INSTRUCTIONS Refer to the lighting instructions on the outside cover of the burner housing. Again, if the unit locks out on safety, main power to the unit must be manually interrupted for a 30 second reset period before the heater can be restarted. NOTE: On initial installation, the unit may lock out on safety owing to the length of time required to bleed air from the gas piping system. 18. RECOMMENDED MAINTENANCE 1.
19. SEQUENCE OF OPERATION - GASLITER MICRO 50N The STW-JZ / IW Burner with direct spark ignition, sequence is as follows : 1. Upon a call for heat by the line voltage Thermostat or "ON/OFF" switch, the Blower and the 120/24 volt Transformer are powered simultaneously with 115 volts. 7. Once the flame sensor determines there is a steady flame established, the spark igniter is then de-energized. 1a.
20. WIRING DIAGRAM WITH 120 VOLT THERMOSTAT OPERATION CARWASH STW-JZ / IW LEAVE JUMPER IN UNLESS 24V RELAY IS BEING INSTALLED THERMOSTAT OPTIONS: INSTALL 120V THERMOSTAT IN SERIES WITH 3 PRONGED PLUG RECEPTACLE . REMOVE 3 WIRE CORD FROM HEATER AND INSTALL IN SERIES WITH 120V SUPPLY TO HEATER TERMINAL BLOCK.
21. TROUBLESHOOTING GUIDE VOLTS APPLY 115 VOLTS—GREEN LIGHT IS ON ON 24V OPTION ONLY: THE SWITCHING RELAY ENERGIZES, SENDING 115 VOLTS TO THE BLOWER SET THERMOSTAT TO CALL FOR HEAT CHECK IF 115 VOLTS PRESENT AT BLOWER IF SO............REPLACE DEFECTIVE BLOWER COMBUSTION AIR BLOWER STARTS NO ON 24V OPTION ONLY: CHECK FOR II5V FROM SWITCHING RELAY. CHECK 24V SIDE OF RELAY VOLTAGE. CHECK 115V LINE SIDE OF RELAY VOLTAGE. CHECK OPERATION OF BOTH CIRCUITS. YES IF NO SWITCHING IS TAKING PLACE......... ....
cont’d MAIN BURNER LIGHTS NO YES • CHECK FOR GOOD SPARK AT IGNITER..... (SEE PREVIOUS PAGE) • CHECK OUTPUT VOLTAGE FROM CONTROL TERMINALS....IF NONE REPLACE CONTROL. • CHECK FOR 25 VAC ACROSS GAS VALVE. • CHECK ELECTRICAL WIRING BETWEEN IGNTION CONTROL AND GAS VALVE.... IF OK, .........REPLACE GAS VALVE. CONTROL IS NOT SENSING FLAME WITHIN THE 21 SECOND TFI AND IS STILL TRYING TO LIGHT SPARK STOPS WHEN BURNER LIGHTS NO YES • CHECK CONTINUITY OF SENSOR CABLE AND GROUND WIRE.
TERMINAL BLOCK 22. WIRING DIAGRAM WITH FIELD INSTALLED 24 VOLT OPTION 24 volt Thermostat Connections (with jumper removed) THERMOSTAT OPTIONS: 120V THERMOSTAT: INSTALL IN SERIES WITH 3 PRONGED PLUG RECEPTACLE, RE-INSTALL TR./TW JUMPER. ALTERNATIVELY REMOVE 3 WIRE CORD FROM HEATER, INSTALL THERMOSTAT IN SERIES WITH 120V SUPPLY TO HEATER TERMINAL BLOCK.
23. SPARK IGNITION CIRCUIT The step-up transformer in the ignition control provides spark ignition at 30,000 volts (open circuit). To check the spark ignition circuit, proceed as follows.
24. START-UP SHEET COMMISSIONING REPORT AS PER I&O MANUAL AND LOCAL CODES CONTRACTOR NAME: ................................................................................DATE................................ ADDRESS:............................................................................................................................................ .........................................................................................................................................................
TO BE COMPLETED BY THE LICENSED INSTALLER TUBE HEATER COMMISSIONING REPORT TYPE OF GAS: NG LP DOES BUILDING HAVE A NEGATIVE CONDITION: YES NO IF THIS IS A HIGH ALTITUDE AREA WHAT IS THE ALTITUDE ABOVE SEA LEVEL Feet DOES APPLICATION REQUIRE FRESH AIR TO BURNER YES NO IS HEATER EXPOSED TO CHEMICAL OR CORROSIVE ATMOSPHERE: YES NO ARE ACTUAL MINIMUM CLEARANCES AS PER TABLE 3 YES NO CAN HEATER BE AFFECTED BY OVERHEAD CRANES / VIBRATION YES NO ARE GAS SUPPLY LINES ADEQUATELY SIZED FOR SYSTEM
25.
90 degree Aluminized Steel Elbow Kit* *Kit includes: elbow, coupler, reflector and plate hanger. For 180 degree Elbow Applications order 2 x 90 degree Elbow kits.
Low Voltage Thermostat (24 Volts) JS-0569-XX 24 Volt Option: Single heater per Thermostat for field mounting in Burner housings (TruTemp or 24 Volt Thermostat extra). JS-0568-KT 24 Volt Option: Multiple Heaters per Thermostat JM-0303 –KT ( for field mounting.
Hanging Chain - (box of 50ft) JL-0798-XX Touch Up Paint - High Temp, 369g aerosol can JA-0587-XX JA-0780-XX Tube Protection Screen -5 feet long JS-0509-XX-P Side Reflector Extension l0” deep l0ft long Each Page 35 GP-MSJW-CX-07B STW-JZ / IW Manual RD: Sept, 2005 RL: 7B KH
26.
LIMITED WARRANTY CERTIFICATE FOR GAS-FIRED INFRA-RED LOW INTENSITY TUBE HEATERS: STS-JZ / IQ, STV-JZ / IV, STW-JZ / IW, SPW-JZ / IWP & STR-JZ SERIES The Manufacturer warrants that this product is free from defects in material or workmanship under normal use and service subject to the terms of this document.