Press the Select button until “dC” appears on
display
3
3
Using the “+” or “-” buttons adjust the damper
cycling CLOSE time
4
4
The number is the minutes the ventilation damper will be closed after
the damper had been open and the fan is still operating for any
reason.
Range 1-480 minutes – Default 20 minutes.
Set the damper cycling CLOSE time
Ventilation Damper Cycling