Operational Characteristics: CME656
Cycle Times (minutes):
System Pressures (PSIG):
Refrigerant Charge, R-404A
Air cooled: 36 ounces
Water cooled: 26 ounces
Typical Compressor Amps
Freeze: single phase = 6.5 - 8;
three phase = 4.5 - 5
Harvest: single phase=9-10; three phase
=5.5-6
Typical Harvest Ice Weight
6.5 - 7 lb.
Water Cooled:
Discharge Pressure: 245 PSIG
Hi Pressure Cuts Out at: 450 PSIG
Fan Control Switch - for units so equipped:
CutIn:240PSIG+-20PSIG
Cut Out: 190 PSIG+-10PSIG
CME256, 506, 656, 806: AutoIQ™ Cubers
January 2002
Page 29
Air Cooled 70
o
F. indoor air, 50
o
F. water 90
o
F. indoor air, 70
o
F. water
Freeze 14 - 15 15 - 16
Harvest 1:30 1:30
Water Cooled 70
o
F. indoor air, 50
o
F. water 90
o
F. indoor air, 70
o
F. water
Freeze 15 - 16 16 - 17
Harvest 3 2
Air Cooled 70
o
F. indoor air, 50
o
F. water 90
o
F. indoor air, 70
o
F. water
Suction: End of Freeze 25 - 27 24 - 26
Suction: Peak in Harvest 83 - 87 84 - 88
Discharge: 5 minutes into Freeze 215 - 225 290 - 300
Discharge: Minimum in Harvest 195 - 205 210 - 220
Water Cooled 70
o
F. indoor air, 50
o
F. water 90
o
F. indoor air, 70
o
F. water
Suction: End of Freeze 24 - 26 24 - 26
Suction: Peak in Harvest 85 - 90 80 - 85
Discharge: 245 PSIG 245 PSIG
Discharge: Minimum in Harvest 180 - 190 190 - 200