Service Manual

Configuration
A remote low side cuber system includes several
sub systems: an ice making section, a remote
compressor package, and a remote air cooled
condenser. Additionally, there are several models
of each sub-system and this manual covers all of
them.
The ice making sections are designed for use
indoors in a controlled environment. The remote
compressor packages and condensers are
designed to operate outdoors. Each sub-system
has limits for power, water and temperature.
Operational Limitations:
Minimum Maximum
Air Temp (IMS) 50
o
F 100
o
F.
Air Temp (CU) -20
o
F. 120
o
F.
Water Temp 40
o
F. 100
o
F.
Water Pressure 20 psi 80 psi
Voltage (IMS) 104 126
Voltage (CU) 198 253
IMS = Ice Making Section, CU= Condensing Unit
Do Not operate the machine in conditions beyond
these limitations. Doing so will void the warranty.
Scotsman ice systems are designed and
manufactured with the highest regard for safety
and performance. They meet or exceed the
standards of UL and NSF.
Scotsman assumes no liability of responsibility of
any kind for products manufactured by Scotsman
that have been altered in any way, including the
use of any part and/or other components not
specifically approved by Scotsman.
Scotsman reserves the right to make design
changes and/or improvements at any time.
Specifications and design are subject to change
without notice.
Warranty
Refer to the warranty coverage in effect when the
equipment was sold. Warranty statements are
included with each product.
Systems:
Each sub-system is a separate entity that carries
its own model and serial number. They must be
combined to create a remote cuber low side
system.
Prodigy Eclipseä 1200, 1400, 1800, 2000
August 2008
Page 2
System Information
Prodigy
Eclipse
System Size
Condensing Unit (CU) Ice Making Section (IMS)
Compressor Package Condenser
Model Electrical Model Electrical Model Electrical
1200 C1200CP-32A 208-230/60/1 ERC1086-32A 208-230/60/1 EH330SL-1A or
EH330ML-1A
115/60/1
1200 C1200CP-3A 208-230/60/3
1400 C1410CP-32A 208-230/60/1
ERC1086 -32A 208-230/60/1
EH430SL-1A
or
EH430ML-1A
115/60/1
1400 C1410CP-3A 208-230/60/3
1800 C1800CP-32A 208-230/60/1 ERC2086-32A 208-230/60/1
1800 C1800CP-3A 208-230/60/3
2000 C2000CP-32A 208-230/60/1
2000 C2000CP-3A 208-230/60/3
Notes: Voltage Codes are at the
end of the model number. Codes
read Voltage/Hertz/Phase. Those
related to these products include:
-1 = 115/60/1
-3 = 208-230/60/3
-32 = 208-230/60/1
Pre-charged tubing kits are required to interconnect the IMS to the
CP.
·
20 foot: 3RTE20-EH, 35 foot: 3RTE35-EH,
·
50 foot: 3RTE50-EH, 75 foot: 3RTE75-EH
Interconnecting 24 volt control wire ships with the CP unit.
Two circuit condenser ER2C1316-32 may be used with C1410CP.