Service Manual
Operational Characteristics 800 lb system
Cycle Times @ Condenser Temp/Cabinet Temp/Water Temp in degrees F.
System Pressures @ Condenser Temp/Cabinet Temp/Water Temp in degrees F
Headmaster maintains a minimum discharge
pressure during freeze of:
·
217 PSIG + 25, -15 PSIG
CPR Valve Setting: 55 - 60 PSIG.
Note: CPR allows a maximum low side pressure at
the CP unit’s compressor. Maximum only occurs
during harvest.
Refrigerant Charge
·
232 oz
Compressor Amps
·
Single Phase - 6 to 8
·
Three Phase - 5 to 7
Batch Weight: 8 lb
Discharge Pressure Cut Out Switch
·
Cuts Out at: 450 PSIG
·
Resets at: 350 PSIG
Prodigy Eclipseä 600, 800, 1000
February 2008
Page 48
70/70/50 90/90/70 120/110/100
Freeze 10 to 12 minutes 13 to 15 minutes 19 to 21 minutes
Harvest 1 to 1.5 minutes 1 to 1.5 minutes .5 to 1 minute
70/70/50 90/90/70 120/110/100
Suction at Ice Making Section, end of Freeze 26 to 31 PSIG 26 to 31 PSIG 30 to 35 PSIG
Suction at Ice Making Section, Harvest - Peak 85 to 105 PSIG 105 to 125 PSIG 140 t0 160 PSIG
Discharge at Condensing Unit: Freeze - 5 minutes in 230 to 250 PSIG 250 to 270 PSIG 330 to 350 PSIG