User's Manual Part 1

Working in Easy mode
40
Step
Description
The detected logger switches from the right-hand to the left-hand window on the
Commander screen. The coloured background of the read data reflects the
probability of a leak.
No colour
Leak probability low,
leak threshold was not exceeded
Grey
Leak probability not available,
logger in config. mode,
(was switched off during or after the measurement)
Other colour
Leak probability high!
Leak threshold exceeded!
The colour reflects approximately the frequency of the
leak noise:
Blue
Yellow
0 Hz
2,500 Hz
If a logger’s comment is on a red background, this means its battery is weak.
3 The Stop and Start buttons can be used to cancel and continue reading at any
time.
The procedure finishes automatically once the Commander has received and
saved the measured data from all the loggers in the group.
During “Patrolling”, the complete measured data set is only transferred
to the Commander from loggers in leak status (see page 14). To save
power, if the quietest noise in a measurement is below the programmed
leak threshold, the loggers will only send a small packet to the
Commander, with the level and frequency of this noise. If necessary, the
complete measured data of these loggers can be called up using single
interrogation in Professional mode (see page 54).
If a logger could not be read, it may have been switched off, not ready for
wireless operation or it was outside the Commander’s wireless range.
4
You can immediately view the data of a logger that has just been read. To do so,
select the respective logger in the left-hand window on the screen.
Result: The logger’s measured data is shown (see page 42). Use the ESC
button to return to the main menu.