Product Overview
Dec 2011 Manufactured by Secop for Danfoss - DEHC.ED.402.O3.02 / 520N0311 1/2
SC18CLX.2
LBP Compressor
R404A/R507
208-230V 60Hz
General
Code number 104L2195
Approvals EN 60335-2-34, UL984
Compressors on pallet 80
Application
Application LBP
Frequency Hz 50 60
Evaporating temperature °C – -45 to -10
Voltage range V – 187 - 254
Max. condensing temperature continuous (short) °C – 55 (60)
Max. winding temperature continuous (short) °C – 125 (135)
Cooling requirements
Frequency Hz 50 60
Application
LBP MBP HBP LBP MBP HBP
32°C – – – F
2
– –
38°C – – – F
2
– –
43°C – – – F
2
– –
Remarks on application:
Motor
Motor type CSR
LRA (rated after 4 sec. UL984), HST | LST A 27.3 –
Cut in Current, HST | LST A 27.3 –
Resistance, main | start winding (25°C) Ω 2.6 9.5
Design
Displacement cm
3
17.68
Oil quantity (type) cm
3
600 (polyolester)
Maximum refrigerant charge g 1300
Free gas volume in compressor cm
3
1460
Weight without electrical equipment kg 13.9
Dimensions
Height mm A 219
B 213
B1 193
B2 110
Suction connector location/I.D. mm | angle C 9.7 | 37°
material | comment Cu-plated steel | Al cap
Process connector location/I.D. mm | angle D 6.5 | 37°
material | comment Cu-plated steel | Al cap
Discharge connector location/I.D. mm | angle E 6.5 | 37°
material | comment Cu-plated steel | Al cap
Oil cooler connector location/I.D. mm | angle F –
material | comment –
Connector tolerance I.D. mm ±0.09
Remarks:
S =Staticcoolingnormallysufcient
O = Oil cooling
F
1
= Fan cooling 1.5 m/s
(compressor compartment temperature
equal to ambient temperature)
F
2
= Fan cooling 3.0 m/s necessary
SG =Suctiongascoolingnormallysufcent
– = not applicable in this area