Installation Instructions

Securitron
®
Netlink
Power Monitoring Module
Specifications
Certifications
UL 294 Listed
UL603 Listed
UL1076 Listed
ULC-S318 Listed
ULC-S319 Listed
CSA C22.2 #205
Shipping Weight
.25 lbs
Dimensions
4" x 2.5" x 1.5"
[101.6mm x 63.5mm x 38.1mm]
Electrical
Input
x Operating Voltage: 8 to 30 VDC
x Operating Current: 60 mA nominal
Network Data Rate: 10/100 Mbps
Voltage Measurement Range:
0 to 30 VDC ±3%
Current Measurement Range:
0 to 20 A ± 0.1 A + 5% of reading
Event
x Input: 9 to 30 VDC
x Current: 15 mA Max
Output 1 & 2 Current: 50 mA maximum
Class 2 power limited wiring must be separated
from non-power limited wiring by a minimum
of 1/4 inch and must use separate knockouts
The installation and all wiring methods shall be in
accordance with ANSI/NFPA70 and all local codes.
For ULC compliance, installation and all wiring
methods shall be in accordance with the Canadian
Electrical Code, C22.1, Part I, Section 32.
All input/output wiring to the module shall be
located within the same room (3 m. max.).
The remote control features have
not been investigated by UL.
Product Description
The Securitron Netlink NL4 module is a network
appliance which may be used with Securitron AQL
power systems to provide remote monitoring
of the power system and connected devices.
The NL4 provides four ports for connection
to Securitron power supply boards.
The Securitron Netlink module monitors power
supply system status over a local or wide area
network and provides values such as output voltage,
fault status, battery voltage, battery charging
current, fire alarm status, and temperature. In
addition, automated battery tests may be run
manually, or scheduled to happen automatically.
Automated alerts may be sent via email or SNMP
on any detected fault condition, service due date
approaching, battery condition, fire alarm activation,
or on a time basis for status updates on regular
intervals. A time and date stamped log of the past
1000 events is kept and may be viewed on demand,
or immediately on an alert occurrence. When all
parameters are in range, the log is updated once per
selected interval with a snapshot of current values.
All Securitron Netlink modules provide a voltmeter
input, event input (for monitoring devices such as the
enclosure tamper switch), and one or two current
sensors. Internal temperature is also sensed, and
the NL4 also includes a 6 foot external temperature
probe for monitoring room temperature.
Manual covers Firmware Rev 8.07l-45
Older firmware revisions may not have all features described.
See the latest firmware release notes at
ht tp://www.lifesafetypower.com/support/software-firmware-dow nloads
Resetting the Securitron Netlink
If the user name or password is unknown for a Securitron Netlink board, press
and hold the Reset button located next to the backup battery for 10 seconds
to return these values to default. Pressing the Reset button for 30 seconds
will also reset the IP address, certificate, and Cipher Suite to default.
Upgrading Securitron Netlink Firmware
The browser history/cache should be cleared after performing the
firmware upgrade and before accessing the Securitron Netlink again
to prevent any cached pages from giving outdated information.
See page 23 for detailed steps for firmware upgrades
17