Power System Monitoring & System History
Any power supply connected to a device input will provide the following parameters:
Device ID
This is the identifying label for the device. The FP-1 or FP-2 label is given by the Securitron
Netlink and is not user settable. Also displayed is the model number of the power supply.
Output Voltage
This is the measured system output voltage (in Volts DC) of the supply, as
measured directly out of the power supply engine within the power supply
board. This voltage is distributed to the outputs of the supply.
AC Fault Status
Indicates whether the supply is reporting a low or missing AC voltage. "No" on a green
background indicates that no problem is being reported. "Yes" on a yellow background
indicates an AC Fault condition. See the power supply manual to troubleshoot.
System Fault Status
Indicates whether the supply is reporting a System Fault condition. "No" on a green
background indicates that no problem is being reported. "Yes" on a yellow background
indicates a System Fault condition. See the power supply manual to troubleshoot.
Battery Voltage
Indicates the measured battery voltage in Volts DC. This field only indicates the terminal voltage of
the battery set and does not necessarily indicate the condition or state of charge of the battery set.
Battery Chg Current
This field indicates the charge current being applyied to the battery set (in Amps DC). This field
only represents charge into the battery and does not show battery discharge current. Use the
Securitron Netlink current sensor to measure both charge and discharge current (See Page 21).
FAI Status
This field indicates the status of the FAI Input of the supply. "Inactive" on
a green background indicates that the FAI input is not activated. "Active"
on a red background indicates that the FAI input is activated.
FAI Latch
This field indicates the status of the FAI Latch Input of the supply. If the Latch Input is being
used and the FAI Input is active and latched, this field will show "Active" on a red background.
If FAI Latch is not being used this field will show "Inactive" on a green background.
AC Fault Count
This field shows the number of AC Faults detected since the last fault counter reset.
When new, a supply may contain a random number in this field and the counter
should be reset (in the Power Supply Settings section) before being used.
System Fault Count
This field shows the number of System Faults detected since the last reset of the fault
counter. A supply may contain random data in this field when new and the counter
should be reset (in the Power Supply Settings section) before being used.
Battery Installed Time
This field displays the battery runtime in hours since the last reset of the battery
runtime counter. The battery runtime field may display random data on a new
supply and should be reset on the Power Supply Settings section before use. This
Runtime is independent of the Battery End-of-Life / Bat. Replacement Date.
Batt Tests Performed
The total number of automated battery tests performed (See Page 21)
Battery Tests Failed
The number of failed battery tests that have occurred (See Page 21)
System Installed Date
This field allows the installer to enter the initial installation
date for the power supply as a service record.
Total Power-up Time
This field displays the total power-up time in hours for the supply. This value cannot be reset. It is
normal for several hours to show in this field on a new supply, due to burn-in testing at the factory.