Installation Instructions

Power Supply Settings
The power supply section shows the programmable settings for the Securitron AQL power supply.
The following parameters are available:
Battery Charge Selector
Select the proper battery size range
for optimal charging rate.
AC Fault Reporting Delay
Select the desired delay for reporting an AC fault in
hours, minutes, and seconds. Note that this delay
will affect the AC Fault LED and relay as well as email
reporting. Check your local codes regarding fault delays.
System Fault Reporting Delay
Select the desired delay for reporting System fault
conditions in hours, minutes, and seconds. Note that
this delay will affect the Sys Fault LED and relay as well
as email reporting. This setting should be used with
caution, as intermittent faults may be masked by a fault
delay. System Fault delays should typically be kept to
5 seconds or less to prevent critical faults from being
masked. Check your local codes regarding fault delays.
Reset Timer for New
Battery Installation
Select this option after installing a new battery
set in order to reset the battery replacement alert
counter. The Securitron Netlink uses this counter
along with the user-entered “Battery Rated
Life” to calculate the next battery replacement
date. See Battery Settings, previous page.
Enter Installation Date
Enter the date the system was initially installed.
This value is only for the user’s information
and is not used by the Securitron Netlink.
Reset AC & System Fault Counts
Selecting this option will reset the AC and
System Fault counters. This is typically done
after testing or servicing the system.
After entering the values or selecting the
appropriate options, click the Apply button
at the bottom of the “Power Supply Settings”
area. These settings will take effect immediately
without rebooting the Securitron Netlink
Current Sensor Calibration
The Current Sensor Calibration block is at the bottom of the power supply page. This section
allows the current sensor to be calibrated to allow the most accurate current readings.
To perform the calibration
1 Ensure the red and orange leads of the current
sensor are disconnected and that the white
cable on the current sensor is connected
to the Securitron Netlink board.
2 After the red and orange leads are disconnected,
click the Zeroing button. A warning message will
appear, reminding you to make sure the current
through the sensor is zero (by disconnecting the
red and orange leads on the current sensor).
3 Click OK, and the Securitron Netlink will
self-calibrate to the current sensor.
4 Ensure the current reading on the home page is
zero (or very close to zero) before reconnecting the
current sensor's red and orange leads. If the reading
is not zero, repeat the calibration procedure.
Typical power Supply Page (bottom portion)
38