Typical Installation
& Wire Routing
Actual configuration and wire routing will vary
based on the components installed in your system.
The following guidelines should be
followed for installation:
Class 2 Power limited wiring must be separated
from nonpower limited wiring by a minimum
of 1/4" and must use separate knockouts.
Any wiring passing through knockouts in the
bottom or top surfaces of the enclosure must
be enclosed in rigid or flexible metal conduit.
Canadian Installations – For permanently
connected equipment, a readily accessible
disconnect device shall be incorporated external
to the equipment. Output circuits not connected
to removable terminal strips shall also utilize
a readily accessible disconnect device.
Securitron AQL6, 102, 104
Securitron AQL4
(Typical installation)
6