Programming instructions
Digital Monitoring Products  XR200-485 Programming Guide
26
STATUS LIST
XR200-485 Programming Guide  Digital Monitoring Products
27
STATUS LIST
Status List
11.1 
STATUS LIST
  Status List 
This function allows you to select the zone alarms and troubles, and system monitor 
troubles displayed at the keypads. The Status List function operates automatically 
when the keypad is not performing any other function. Status list displays for 
addresses 9 through 16 automatically show when a corresponding address 1 through 
8 is entered.
The keypad stays in the Status List until the user arms or disarms or selects a menu 
option. Status List alternates with the Armed Status on keypad addresses selected 
in the Menu Display - Armed Status section. You can choose to have System Monitor 
troubles placed in the list, the different zone types placed in the list, and at which 
keypad addresses they display.
11.2 
DISPLAY KEYPADS:
  Display Keypads
This option denes which keypad addresses display the various status information. 
Any combination of addresses can be entered to display the status items that follow.  
If you do not want a particular status item to display, do not enter any addresses.
11.3 
SYS TRB  12345678
  System Monitor Troubles
Species the addresses where any trouble on a System Monitor displays. The System 
Monitors include the following:
    AC Power
    Battery Power
    Closing Check 
    Panel Box Tamper 
    Phone Line 1 
    Phone Line 2  (requires the 893 or 893A Dual Phone Line Module)
The name of the System Monitor is placed in the Status List and the keypad steady 
trouble buzzer sounds. The buzzer remains on until any top row Select key is 
pressed on the keypad. The name remains in the list until the condition is restored.
11.4 
FIRE 12345678
  Fire Zones
Species the addresses where all re zone alarms and troubles display. The zone 
name displays and, if it is a trouble condition, the keypad steady trouble buzzer 
sounds. The buzzer remains on until any top row Select key is pressed. The name 
remains in the list until the user clears it with the Sensor Reset function.
When using the Security Command LCD Keypads or the 630F Remote Fire Command 
Center, the panel provides distinct speaker tones from the keypad for Fire: 
On - Fire zone alarm and Bell Output or Fire Bell Output is ON.
Off - Alarm Silence