Programming instructions
Digital Monitoring Products  XR200-485 Programming Guide
34
ZONE INFORMATION
XR200-485 Programming Guide  Digital Monitoring Products
35
ZONE INFORMATION 
15.4 
ZONE TYPE:   BLANK
  Zone Type
The Zone Type denes the panel response to the zone being opened or shorted. 
This is called the Alarm Action. There are up to 13 possible alarm action responses 
depending on the zone type and any restrictions it may have. See Sections 18.4 and 
18.5 in the Appendix for Zone Type information.
When you assign a Zone Type to a zone, responses are made automatically for the 
zone. There are 12 Zone Types to choose from. Application descriptions for each 
zone type can be found in Section 18.4 Zone Descriptions in the Appendix.
To enter a new Zone Type, press any Select key. The display lists all of the available  
Zone Types four at a time.
 - -  NT  DY  EX
  Blank, Night, Day, or Exit. Press COMMAND for additional zone types.
FI  PN  EM  SV
  Fire, Panic, Emergency, or Supervisory. Press COMMAND for additional zone types.
A1  A2  FV  AR
  Auxiliary 1, Auxiliary 2, Fire Verify, or Arming (keyswitch). Press the Back Arrow key 
to display the previous zone types. When the Zone Type you want displays, press the 
Select key beneath it.
If you select Blank, Night, Day, Exit, Auxiliary 1, Auxiliary 2, or Arming as the Zone 
Type, the zone must be assigned to an active area. If you select Fire, Fire Verify, 
Panic, Emergency, or Supervisory as the Zone Type, it is a 24-hour zone that is always 
armed and no area assignment is needed. 
Zone Type Specications
The panel contains 12 default zone types for use in conguring the system. These 
zone types provide the most commonly selected functions for their applications. All 
zone types except the Arming zone type can be customized by changing the options 
listed below.
Refer to Section 18.4 in the Appendix for complete zone type descriptions. 
15.5 
FIRE BELL OUT:  0
  Fire Bell Output
This output (1 to 10, 100 to 299) is turned on any time a Fire, Fire Verify, or 
Supervisory zone is placed in alarm. The output is turned off by any the following 
actions:
•  When the User Menu Alarm Silence function is performed.
•  When a valid user code is entered to silence the bell.
•  When the Silence key is pressed on the 630F Remote Fire Command Center.
•  Using the Outputs On/Off function in the User Menu.
•  The expiration of the Bell Cutoff time.
15.6 
PARTITION NO:  1
  Partition Number
Enter the partition number where this zone is being assigned.
15.7 
AREA NO: -
  Area Number
For an Area system, enter the area number where this zone is being assigned. 