15.17 
SWGR BYP  NO  YES
  Swinger Bypass
YES allows the zone to be swinger bypassed by the panel according to the 
specications programmed in Swinger Bypass Trips and Reset Swinger Bypass. The 
Bypass condition displays in the keypad Status List. Selecting NO disables swinger 
bypassing for this zone.
How it works
If within one hour, a zone trips the total number of times AS specied in Swinger 
Bypass Trips, the panel bypasses it until the following conditions occur; the area 
in which the zone is assigned is disarmed, the zone is manually reset through the 
Bypass Zones? keypad User Menu function, the zone remains normal for one hour and 
the Reset Swinger Bypass is YES.
If the zone trips fewer than the specied times within one hour, the bypass trip 
counter returns to zero and the process must repeat.
A swinger bypass report is sent to the receiver if Bypass Reports is YES.
15.18 
PREWARN: 12345678
  Prewarn Addresses
At the start of the entry delay, all keypad addresses selected here display ENTER 
CODE:-. If you want the prewarn to sound at all eight addresses, leave the default 
as shown.
To delete an address, press the matching number on the keypad. To disable 
prewarning at all keypads, press any top row Select key to clear the addresses 
shown. Press the COMMAND key when the address selection is complete.
15.19 
ENTRY DELAY:   1
  Entry Delay
Select the entry timer for this zone. Entry timers 1 to 4 are programmed in System 
Options.
15.20 
RETARD   NO  YES
  Zone Retard
When you select YES, the zone operates with the zone retard delay. The retard 
functions only in zone short conditions.
The zone must remain shorted for the full length of the retard delay before the 
panel recognizes its condition. If you select NO, the zone operates without a retard 
delay.
If the zone is programmed as an Auxiliary 2 or Arming type, the Zone Retard Delay 
timer is counted in minutes. This allows a light sensor, which detects darkness and 
obstructing objects, to be connected to the zone. 
Note: The number entered for Zone Retard Delay is used for all types of zones 
that are programmed for Retard in Zone Information. For example, if you enter a 
15-second delay for Fire zones, there will be a 15-minute delay for Auxiliary 2 and 
Arming type zones.
15.21 
PRESGNL:    NONE
  Presignal Addresses
You can enable any combination of keypad addresses to sound a presignal tone 
during the time a zone is in retard delay. The presignal tone silences when the zone 
restores or the retard delay expires. 
To enable a presignal address, press any top row Select key followed by the number 
of the keypad address. You can enable the presignal for all eight keypad addresses. 
To disable a presignal address press the matching number digit again. Press the 
COMMAND key when the address selection is complete. The Presignal prompt only 
displays when Retard is selected as YES.
15.22 
FAST RSP  NO  YES
  Fast Response
Select YES to provide a zone response time of 167ms. Select NO to provide a normal 
zone response time of 500ms. Zones 100 to 299 have a xed response time of 200ms 
and do not display this prompt.