Programming instructions
Digital Monitoring Products  XR200-485 Programming Guide
44
APPENDIX
XR200-485 Programming Guide  Digital Monitoring Products
45
APPENDIX
BELL    NO  YES
  Bell Action
This option selects the bell output action when a zone under test faults. This option 
allows the panel bell, and/or burglary bell, and/or re bell to turn ON and then OFF 
each time a zone trips (opened or shorted).
NO - Select NO for no bell output action during Walk Test.
YES - Select YES to turn on any bell output for 2 seconds during Walk Test.
PULS - Select PULS to turn on any bell output for 1/4 second during Walk Test. Any 
LX-Bus device output turns on for 1.6 seconds due to the polling cycle.
Once in the Walk Test, walk around and trip each protective device. As each device 
trips, the panel sounds the alarm bells as programmed in Bell Action (described on 
the following page) and then performs an automatic Sensor Reset. Continue tripping 
devices until the entire system is tested. The trip counter on the keypad display 
increments by one each time a device opens or shorts.
TRIPS: XXX    END
  Trip Counter
Displays the number of zone trips during the Walk Test.
•  Each time a selected zone trips, the keypad buzzes for two seconds.
•  Each time an FI, FV, or SV zone is tripped, a Sensor Reset occurs.
END - Press the Select key directly below END to stop the Walk Test. When the Walk 
Test ends or a 20 minute time-out expires, a nal Sensor Reset occurs. The System 
Test End message is sent to the receiver along with Verify and Fail messages for each 
zone under test. Faulted zones then display on the keypad.
SOUTH LOBBY
  Failed Zones Display
ZONE: 10    -FAIL
  For each zone that did not trip (failed) at least once during the Walk Test, the 
keypad displays the zone name and number and buzzes for one second. Press the 
COMMAND key to display the next failed zone.
Local Printer for Walk Test
When the Walk Test is completed, a Verify or Fail message for each zone tested prints to the local printer. 
Enable Walk Test message printing through Printer Reports programming. 
18.4  Keypads Speaker Operation
When using the Security Command LCD Keypads or the 630F Remote Fire Command Center, the panel 
provides distinct speaker tones from the keypad for Fire, Burglary, Zone Monitor, and Prewarn events. The 
list below details the conditions under which the speaker is turned on and off for each event.
Fire  On - Fire zone alarm and Bell Output or Fire Bell Output is ON.
  Off - Alarm Silence.
Burglary  On - Burglary zone alarm and Bell Output or Burglary Bell Output is ON.
  Off - Alarm Silence.
Zone Monitor  On - One time only when a monitored zone is tripped.
  Off - After one tone.
Prewarn  On - During Entry Delay.
  Off - When Entry Delay expires.
18.5  Cross Zoning
Caution must be taken when cross zoning devices to ensure that the Cross Zone Time is long enough to 
allow an intruder to trip both devices before the time expires. A Cross Zone Time that is too short may 
allow an intruder to trip the devices and have just a zone fault report sent to the central station.
When a Cross Zoned zone is tripped a FAULT report is sent to the SCS-1/SCS-1R Receiver. When two Cross 
Zoned zones trip within the Cross Zone Time, both zone reports are sent to the receiver as ALARM signals. 
For example, if zones 1 and 2 are Cross Zoned zones, and only zone 1 trips, a FAULT report is sent to the 
receiver for zone 1. If zone 1 trips and zone 2 trips within the Cross Zone Time, an ALARM report is sent to 
the receiver for zone 1 and zone 2. 