User manual
SmartBox
®
 1 / SmartBox
®
 2 / SmartBox
®
 3 
6 / 16  Part No. 28 100 57 e 
PROGRAMMING 
Menu 
Input function 
Input value 
0.Exit 
Press [Enter] to return to display mode 
1.Measure 
probe 
Select probe measuring range (see type label of the 
probe) - default value is 250 mbar 
________mbar 
Standard probe 
max. Tank height for 
heating oil 
water 
100mbar 
1.20 m 
1.00 m 
150mbar 
1.80 m 
1.50 m 
160mbar 
1.90 m 
1.60 m 
200mbar 
2.40 m 
2.00 m 
250mbar 
2.90 m 
2.50 m 
400mbar 
4.70 m 
4.00 m 
500mbar 
6.00 m 
5.00 m 
1.000mbar 
12.00 m 
10.00 m 
2.000mbar 
24.00 m 
20.00 m 
3.000mbar 
36.00 m 
30.00 m 
5.000mbar 
60.00 m 
50.00 m 
Set mbar 
by 
Calibration 
Is only indicated if item 10. Set h 
or 11. Set V has been activated 
2.Liquid 
Select the medium 
_______kg/m³ 
Medium 
Measuring range kg/m³ (15 °C) 
Heat. oil 
Measuring range kg/m³ (15 °C) 
Water 
  845 kg/m³ - default setting 
Diesel 
  999 kg/m³ 
Biodiesel 
  830 kg/m³ 
RME, FAME 
  880 kg/m³ 
Rape oil 
  880 kg/m³ 
Palm oil 
  915 kg/m³ 
Motor oil 
  910 kg/m³ 
AdBlue 
  865 kg/m³ 
Regular 
gasoline 
 1090 kg/m³ 
Premium 
gasoline 
  743 kg/m³ 
Density valve 
  750 kg/m³ 
by 
Calibration 
Entry of a specific probe with 
different measuring range 
If the density of the stored medium is unknown, the reference height can be entered in menu 
item “10.Trim height” To do this, determine the current fill level in mm, deduct 1.0 cm from it 
and enter the resulting value - click YES to confirm the entry. 
Should the current fill level be less than 75%, we urgently recommend that you adjust the 
value after the next refuelling to achieve good measuring accuracy. 